2018-03-01 11:51:16PERMIT # 18020929
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FIRE COMMENTS:
  
 1) PLEASE ADDRESS COMMENTS UNDER BUILDING REVIEW.
  
 2) PLEASE PROVIDE THE DISTANCE FROM THE TRAILER TO THE
 LIFT STATION SHOWN ON THE SITE PLAN. DISTANCES FROM
 OTHER STRUCTURES SHALL COMPLY WITH THE FOLLOWING:
  
 PER NFPA 241 ? STANDARD FOR SAFEGUARDING CONSTRUCTION,
 ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2
 TEMPORARY CONSTRUCTION TRAILERS SHALL BE SEPARATED FROM
 ADJACENT TRAILERS OR STRUCTURES IN ACCORDANCE WITH
 TABLE 4.2.1. PER TABLE 4.2.1:
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET.
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET.
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET.
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET.
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 60 FEET.
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 3) DRAWINGS WILL BE STAMPED, INITIALED, AND DATED BY
 THE FIRE DEPARTMENT AFTER ALL PLAN REVIEWER COMMENTS
 HAVE BEEN SATISFIED.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 [email protected]
  