| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | FIRE COMMENTS: |
| | |
| | 1) PLEASE ADDRESS COMMENTS UNDER BUILDING REVIEW. |
| | |
| | 2) PLEASE PROVIDE THE DISTANCE FROM THE TRAILER TO THE |
| | LIFT STATION SHOWN ON THE SITE PLAN. DISTANCES FROM |
| | OTHER STRUCTURES SHALL COMPLY WITH THE FOLLOWING: |
| | |
| | PER NFPA 241 ? STANDARD FOR SAFEGUARDING CONSTRUCTION, |
| | ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2 |
| | TEMPORARY CONSTRUCTION TRAILERS SHALL BE SEPARATED FROM |
| | ADJACENT TRAILERS OR STRUCTURES IN ACCORDANCE WITH |
| | TABLE 4.2.1. PER TABLE 4.2.1: |
| | 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 30 FEET. |
| | 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 35 FEET. |
| | 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 40 FEET. |
| | 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 45 FEET. |
| | 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 60 FEET. |
| | **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL |
| | BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC |
| | SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE. |
| | |
| | 3) DRAWINGS WILL BE STAMPED, INITIALED, AND DATED BY |
| | THE FIRE DEPARTMENT AFTER ALL PLAN REVIEWER COMMENTS |
| | HAVE BEEN SATISFIED. |
| | |
| | |