Plan Review Notes
Plan Review Notes For Permit 18020922
Permit Number 18020922
Review Stop G
Sequence Number 1
Notes
Date Text
2018-03-01 14:17:39DENIED
  
 1. THE DETAILS ON OF THE CATHODIC PROTECTION ARE NOT
 CLEAR AS IT IS A COPY OF A COPY; SIZE (LBS) & A NUMBER
 OF MAGNESIUM BAG(S), SIZE & TYPE OF ANODE CABLE. A
 CATHODIC PROTECTION SYSTEM SHALL BE REQUIRED PER NFPA
 58 SECS. 5.2.1.11, 6.6.6.1 (I) AND SHALL BE MONITORED
 PER NFPA 58 SEC.6.6.6.1 (J). WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. NEED REGULATORS MANUAL, WHEN INSTALLED OUTDOORS
 SHALL BE DESIGNED, INSTALLED OR PROTECTED SO THEIR
 OPERATION WILL NOT BE AFFECTED BY THE ELEMENTS. PROVIDE
 DOCUMENTATION FROM THE MANUFACTURER THAT THE REGULATORS
 ARE APPROVED FOR EXTERIOR USE AND HAVE IT ON SITE AT
 THE TIME OF INSPECTIONS. NFPA 58-11 SEC. 6.8.1.5.
  
 3. NFPA 37, SECTION 4.1.4, ENGINES LOCATED OUTDOORS.
 ENGINES, AND THEIR WEATHERPROOF HOUSINGS, IF PROVIDED,
 THAT ARE INSTALLED OUTDOORS SHALL BE LOCATED AT LEAST 5
 FT FROM OPENINGS IN WALLS AND AT LEAST 5 FT FROM
 STRUCTURES HAVING COMBUSTIBLE WALLS. A MINIMUM
 SEPARATION SHALL NOT BE REQUIRED WHERE EITHER OF THE
 FOLLOWING CONDITIONS EXIST;
  
 (1) ALL WALLS OF THE STRUCTURE THAT ARE CLOSER THAN 5
 FT FROM THE ENGINE ENCLOSURE HAVE A FIRE RESISTANCE
 RATING OF
 AT LEAST 1 HOUR.
  
 (2)*THE WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF
 NONCOMBUSTIBLE MATERIALS AND IT HAS BEEN DEMONSTRATED
 THAT A FIRE WITHIN THE ENCLOSURE WILL NOT IGNITE
 COMBUSTIBLE MATERIALS OUTSIDE THE ENCLOSURE.
  
 A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS TIME
 AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED
 UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  