| 2018-03-01 14:17:39 | DENIED |
| | |
| | 1. THE DETAILS ON OF THE CATHODIC PROTECTION ARE NOT |
| | CLEAR AS IT IS A COPY OF A COPY; SIZE (LBS) & A NUMBER |
| | OF MAGNESIUM BAG(S), SIZE & TYPE OF ANODE CABLE. A |
| | CATHODIC PROTECTION SYSTEM SHALL BE REQUIRED PER NFPA |
| | 58 SECS. 5.2.1.11, 6.6.6.1 (I) AND SHALL BE MONITORED |
| | PER NFPA 58 SEC.6.6.6.1 (J). WPB AMENDMENTS TO THE FBC |
| | SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 2. NEED REGULATORS MANUAL, WHEN INSTALLED OUTDOORS |
| | SHALL BE DESIGNED, INSTALLED OR PROTECTED SO THEIR |
| | OPERATION WILL NOT BE AFFECTED BY THE ELEMENTS. PROVIDE |
| | DOCUMENTATION FROM THE MANUFACTURER THAT THE REGULATORS |
| | ARE APPROVED FOR EXTERIOR USE AND HAVE IT ON SITE AT |
| | THE TIME OF INSPECTIONS. NFPA 58-11 SEC. 6.8.1.5. |
| | |
| | 3. NFPA 37, SECTION 4.1.4, ENGINES LOCATED OUTDOORS. |
| | ENGINES, AND THEIR WEATHERPROOF HOUSINGS, IF PROVIDED, |
| | THAT ARE INSTALLED OUTDOORS SHALL BE LOCATED AT LEAST 5 |
| | FT FROM OPENINGS IN WALLS AND AT LEAST 5 FT FROM |
| | STRUCTURES HAVING COMBUSTIBLE WALLS. A MINIMUM |
| | SEPARATION SHALL NOT BE REQUIRED WHERE EITHER OF THE |
| | FOLLOWING CONDITIONS EXIST; |
| | |
| | (1) ALL WALLS OF THE STRUCTURE THAT ARE CLOSER THAN 5 |
| | FT FROM THE ENGINE ENCLOSURE HAVE A FIRE RESISTANCE |
| | RATING OF |
| | AT LEAST 1 HOUR. |
| | |
| | (2)*THE WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF |
| | NONCOMBUSTIBLE MATERIALS AND IT HAS BEEN DEMONSTRATED |
| | THAT A FIRE WITHIN THE ENCLOSURE WILL NOT IGNITE |
| | COMBUSTIBLE MATERIALS OUTSIDE THE ENCLOSURE. |
| | |
| | A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS TIME |
| | AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED |
| | UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |