| 2018-03-09 14:37:30 | PLUMBING 2ND REVIEW**DENIED** | | | | | | | | | I HAVE READ AND UNDERSTAND YOUR RESPONCE LETTER THAT | | | YOUR PLUMBING SUB WILL BE APPLYING FOR THE SUB PERMIT | | | BUT SINCE YOU HAVE INCLUDED A WATER ISOMETRIC AND | | | FAILED TO ADRESSS THE DISPOSAL OR HOW THE DISPOSAL IS | | | TO BE HANDLED A PLUMBING REVIEW WILL BE DONE AT THIS | | | TIME AND DENIED. | | | | | | | | | 1) THE MAIN BACKFLOW IS FOR THE PROTECTION OF THE | | | CITY'S WATER SUPPLY. ANY BRANCH SUPPLY CONNECTION WOULD | | | REQUIRED A SEPERATE ISOLATION BACKFLOW PER FBC-P 608.1. | | | A SEPERATE PERMIT AND APPLICATION IS REQUIRED AND CAN | | | BE DONE BY YOUR PLUMBING SUB AT A LATER DATE | | | | | | 2) ALL DOCUMENTS PROVIDED ARE REQUIRED TO HAVE A MIN OF | | | 2 COPIES FBC 107.1*NEEDED TO APPROVE THIS PERMIT* | | | | | | ITEM NOT ADDRESSED FROM LAST REVIEW | | | | | | 1) PLEASE PROVIDE THE SIZING OF THE HOLDING TANKS. | | | EXPLAIN THE DISPOSAL PROCESS OF WHO, HOW, AND WHEN IT | | | WILL BE DISPOSED OF. (COPY OF PUMP OUT CONTRACT)* | | | NEEDED TO APPROVE THIS PERMIT** | | | | | | | | | TIM HUNT | | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | 561-805-6695 | | | [email protected] | | | |
|