Plan Review Notes
Plan Review Notes For Permit 18020921
Permit Number 18020921
Review Stop P
Sequence Number 2
Notes
Date Text
2018-03-09 14:37:30PLUMBING 2ND REVIEW**DENIED**
  
  
 I HAVE READ AND UNDERSTAND YOUR RESPONCE LETTER THAT
 YOUR PLUMBING SUB WILL BE APPLYING FOR THE SUB PERMIT
 BUT SINCE YOU HAVE INCLUDED A WATER ISOMETRIC AND
 FAILED TO ADRESSS THE DISPOSAL OR HOW THE DISPOSAL IS
 TO BE HANDLED A PLUMBING REVIEW WILL BE DONE AT THIS
 TIME AND DENIED.
  
  
 1) THE MAIN BACKFLOW IS FOR THE PROTECTION OF THE
 CITY'S WATER SUPPLY. ANY BRANCH SUPPLY CONNECTION WOULD
 REQUIRED A SEPERATE ISOLATION BACKFLOW PER FBC-P 608.1.
 A SEPERATE PERMIT AND APPLICATION IS REQUIRED AND CAN
 BE DONE BY YOUR PLUMBING SUB AT A LATER DATE
  
 2) ALL DOCUMENTS PROVIDED ARE REQUIRED TO HAVE A MIN OF
 2 COPIES FBC 107.1*NEEDED TO APPROVE THIS PERMIT*
  
 ITEM NOT ADDRESSED FROM LAST REVIEW
  
 1) PLEASE PROVIDE THE SIZING OF THE HOLDING TANKS.
 EXPLAIN THE DISPOSAL PROCESS OF WHO, HOW, AND WHEN IT
 WILL BE DISPOSED OF. (COPY OF PUMP OUT CONTRACT)*
 NEEDED TO APPROVE THIS PERMIT**
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION