| 2018-03-09 09:39:13 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. |
| | |
| | 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF |
| | SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, |
| | WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY |
| | SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW |
| | INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230, |
| | 250.50, 250.94, 408.30 (ONLY ONE COPY OF RISER, AIC |
| | LETTER, AND LOAD CALCULAITON WAS PROVIDED. CODE |
| | REQUIRES TWO COPIES OF EACH SHEET SUBMITTED, WITH EACH |
| | SHEET SIGNED BY QUALIFIER OR DESIGN PROFESSIONAL. FBC |
| | 107.1) |
| | 2. CORRECTED. |
| | 3. CORRECTED. |
| | |
| | NEW COMMENT: |
| | |
| | 4. PROVIDE ACCURATE LOAD CALCULATION AND SIZE SERVICE |
| | ACCORDINGLY. LOAD CALC PROVIDED QUOTES NEC 220.32, |
| | WHICH DOES NOT EXIST. CALCULATION APPEARS TO USE THE |
| | DEMAND FACTORS FOR DWELLING UNITS, WHICH CAN NOT BE |
| | USED FOR THIS APPLICAITON. ALL LOADS WOULD BE FIGURED |
| | AT 100% PER NEC 220.42. LOAD CALCULATION MUST BE FOR |
| | ENTIRE SERVICE INCLUDING THE AMOUNTS FOR THE |
| | REFRIGERATION TRAILER, AS WELL AS A LOAD CALCULATION |
| | FOR THE FEEDS TO EACH TRAILER. FEEDERS MUST BE SIZED TO |
| | HANDLE 100% OF NON-CONTINUOUS LOAD PLUS 125% OF THE |
| | CONTINUOUS LOAD. IF THESE CALCULATIONS EXCEED 800 AMPS, |
| | THIS MUST BE DESIGNED BY ENGINEER. PROVIDE CORRECTIONS. |
| | NEC 215.2, 220, 230.42, 408.30; FBC 107.2.1; FS |
| | 471.003(2)(H) |
| | 5. RISER SHOWS # 6 AL WIRE ON A 60 AMP BREAKER TO THE |
| | REFRIGERATION TRAILER. THIS SIZE AL WIRE IS NOT RATED |
| | FOR 60 AMPS. PROVIDE CORRECTION. NEC 310.15(B)(16) |
| | 6. ONE TRAILER IS SHOWN BEING FED FROM 2 DIFFERENT |
| | PANELS, PROVIDE LABEL THAT WARNS OF 2 POWER SOURCES FOR |
| | THIS TRAILER. NEC 230.2(E) |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |