Plan Review Notes
Plan Review Notes For Permit 18020921
Permit Number 18020921
Review Stop E
Sequence Number 2
Notes
Date Text
2018-03-09 09:39:13CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES.
  
 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30 (ONLY ONE COPY OF RISER, AIC
 LETTER, AND LOAD CALCULAITON WAS PROVIDED. CODE
 REQUIRES TWO COPIES OF EACH SHEET SUBMITTED, WITH EACH
 SHEET SIGNED BY QUALIFIER OR DESIGN PROFESSIONAL. FBC
 107.1)
 2. CORRECTED.
 3. CORRECTED.
  
 NEW COMMENT:
  
 4. PROVIDE ACCURATE LOAD CALCULATION AND SIZE SERVICE
 ACCORDINGLY. LOAD CALC PROVIDED QUOTES NEC 220.32,
 WHICH DOES NOT EXIST. CALCULATION APPEARS TO USE THE
 DEMAND FACTORS FOR DWELLING UNITS, WHICH CAN NOT BE
 USED FOR THIS APPLICAITON. ALL LOADS WOULD BE FIGURED
 AT 100% PER NEC 220.42. LOAD CALCULATION MUST BE FOR
 ENTIRE SERVICE INCLUDING THE AMOUNTS FOR THE
 REFRIGERATION TRAILER, AS WELL AS A LOAD CALCULATION
 FOR THE FEEDS TO EACH TRAILER. FEEDERS MUST BE SIZED TO
 HANDLE 100% OF NON-CONTINUOUS LOAD PLUS 125% OF THE
 CONTINUOUS LOAD. IF THESE CALCULATIONS EXCEED 800 AMPS,
 THIS MUST BE DESIGNED BY ENGINEER. PROVIDE CORRECTIONS.
 NEC 215.2, 220, 230.42, 408.30; FBC 107.2.1; FS
 471.003(2)(H)
 5. RISER SHOWS # 6 AL WIRE ON A 60 AMP BREAKER TO THE
 REFRIGERATION TRAILER. THIS SIZE AL WIRE IS NOT RATED
 FOR 60 AMPS. PROVIDE CORRECTION. NEC 310.15(B)(16)
 6. ONE TRAILER IS SHOWN BEING FED FROM 2 DIFFERENT
 PANELS, PROVIDE LABEL THAT WARNS OF 2 POWER SOURCES FOR
 THIS TRAILER. NEC 230.2(E)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  