| 2018-03-30 13:11:48 | RESIDENTIAL (R3) REVISION, SECOND BUILDING REVIEW |
| | CHECKLIST. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | |
| | 1- THIS REVISION IS FOR CONCRETE ROOF TILES. |
| | ORIGINALLY, THE HOUSE WAS DESIGNED WITH METAL ROOFING. |
| | THE DESIGN CRITERIA CONSIDERED FOR THIS HOUSE DIDN'T |
| | INCLUDE THE ADDITIONAL WEIGHT OF THE CONCRETE TILE. SEE |
| | DESIGN CRITERIA ON SHEET S-2 AND S-3. DESIGNER OF |
| | RECORD NEEDS TO REVISE THE DESIGN CRITERIA ACCORDINGLY |
| | SO THE ROOF TRUSSES ARE DESIGNED FOR THE PROPER |
| | LOADING. PROVIDE 2 COPIES. SEC. R301.1 FBC-RESIDENTIAL. |
| | RESPONSE: REPEAT COMMENT. NOT ADDRESSED. DESIGNER OF |
| | RECORD DIDN'T REVISED SHEET S-2 AND S-3. NOTE: REVISION |
| | FEES WILL APPLY. |
| | |
| | IMPORTANT : |
| | TRUSS PACKAGE IS BEING REVIEWED UNDER SUBMITTAL |
| | #18030548. SEE THIS SUBMITTAL # FOR COMMENTS. |
| | |
| | 2- DESIGNER OF RECORD TO SPECIFY NEW ROOF TILE |
| | FASTENING METHOD AS REQUIRED BY SEC. 107.2.1.1 CITY |
| | AMENDMENTS. IF USING SCREWS, THEN SPECIFY SIZE AND |
| | NUMBER OF SCREWS. IF USING ROOF TILE ADHESIVE, THEN |
| | PRODUCT APPROVAL IS REQUIRED. SEE ROOF TILE NOA FOR |
| | LISTED ADHESIVE AND SUBMIT 2 COPIES OF THE ADHESIVE |
| | PRODUCT APPROVAL. |
| | |
| | SEC. 107.2.1.1 FOR ROOF ASSEMBLIES REQUIRED BY THE |
| | CODE, THE CONSTRUCTION DOCUMENTS |
| | SHALL ILLUSTRATE, DESCRIBE AND DELINEATE THE TYPE OF |
| | ROOFING SYSTEM, MATERIALS, FASTENING |
| | REQUIREMENTS, FLASHING REQUIREMENTS AND WIND RESISTANCE |
| | RATING THAT ARE REQUIRED TO BE |
| | INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL |
| | INDICATE COMPLIANCE WITH THE WIND |
| | CRITERIA REQUIRED FOR THE SPECIFIC SITE OR A STATEMENT |
| | BY AN ARCHITECT OR ENGINEER |
| | CER T I F Y IN G SU I TABI L I T Y FOR THE SPECIFIC |
| | SITE MUST BE SUBMITTED WITH THE CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 4- OWES $51.50 FOR NEW EXTERIOR DOOR NOA NO. 15-0413.12 |
| | SUBMITTED. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |