| Plan Review Notes For Permit 18020906 |
| Permit Number |
18020906 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-02-26 16:40:33 | RESIDENTIAL (R3) REVISION, BUILDING REVIEW CHECKLIST. | | | CODE: FBC 5TH EDITION (2014). | | | | | | | | | 1- THIS REVISION IS FOR CONCRETE ROOF TILES. | | | ORIGINALLY, THE HOUSE WAS DESIGNED WITH METAL ROOFING. | | | THE DESIGN CRITERIA CONSIDERED FOR THIS HOUSE DIDN'T | | | INCLUDE THE ADDITIONAL WEIGHT OF THE CONCRETE TILE. SEE | | | DESIGN CRITERIA ON SHEET S-2 AND S-3. DESIGNER OF | | | RECORD NEEDS TO REVISE THE DESIGN CRITERIA ACCORDINGLY | | | SO THE ROOF TRUSSES ARE DESIGNED FOR THE PROPER | | | LOADING. PROVIDE 2 COPIES. SEC. R301.1 FBC-RESIDENTIAL. | | | | | | 2- A) SUBMIT TRUSS PACKAGE (2 COPIES) FOR REVIEW TO | | | VERIFY COMPLIANCE WITH THE REVISED DESIGN CRITERIA. | | | SEC. R301.1 FBC-RESIDENTIAL. | | | | | | B) TRUSS PACKAGE TO BE REVIEWED AND APPROVED BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL. SEC.107.3.4.2 | | | CITY AMENDMENTS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|