| 2018-03-12 15:15:41 | 3/12/2018 **1ST REVIEW DENIED ** |
| | |
| | 1. SIGNATURE OF AN ARCHITECT-ENGINEER IS REQUIRED, NOT |
| | IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODE |
| | 61G15-23.001, FLORIDA STATUTE 471. |
| | 2. WHAT IS THE TURNOVER TIME OF THE POOL VOLUME PER DAY |
| | FBC B 454.1.6.2 |
| | 3. PLEASE PROVIDE THE MANUFACTURES SPECIFICATION FOR |
| | THE MAIN DRAIN GRATE AND SPA DRAIN GATE TO VERIFY |
| | COMPLIANCE WITH ASME/ANSI A112.19.8 COMPLIANT |
| | COVER/GRATE |
| | 4. THE MINIMUM GPM OF 73 GPM SHOWN ON SHEET 1 FOR THE |
| | POOL IS VALID FOR A BATHING LOAD OF 15 PERSONS. YOU |
| | LIST THE BATHING LOAD AS 20 PERSONS WHICH REQUIRES A |
| | MINIMUM FLOW OF 1000 GPM PER FBC B SEC. 454.1.1.1 |
| | SIZING, PLEASE CLARIFY THIS. |
| | 5. PLEASE PROVIDE MANUFACTURES SPECIFICATION ON PUMP |
| | AND HEATER FBC B SEC. 454.1.6.5.14 HEATERS. |
| | 6. PLEASE PROVIDE A COMPLETE PIPING DIAGRAM WPB |
| | AMENDMENTS TO THE FBC SEC. 107.5.1.3 (13) COMMERCIAL |
| | PLUMBING. |
| | 7. IF THE PUMP IS LOCATED ABOVE THE WATER LEVEL OF THE |
| | POOL, THE PUMP SHALL BE SELF-PRIMING FBC 454.1.6.5.4. |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | A SEPARATE PERMIT AND REVIEW SHALL BE REQUIRED FOR GAS. |
| | |