Plan Review Notes
Plan Review Notes For Permit 18020875
Permit Number 18020875
Review Stop B
Sequence Number 2
Notes
Date Text
2018-03-16 11:03:54BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. BUILDINGS AND STRUCTURES LOCATED ON PARCELL'S
 DESIGNATED RESIDENTIAL SHALL COMPLY WITH THE FBC R301
 2. PROVIDE FOUNDATION DETAILS WITH UPLIFT VALUES.
 3. PROVIDE DESIGN WIND LOADS FOR STRUCTURE.
  
 DESIGN CRITERIA
 R301.1APPLICATION.
 BUILDINGS AND STRUCTURES, AND PARTS THEREOF, SHALL BE
 CONSTRUCTED TO SAFELY SUPPORT ALL LOADS, INCLUDING DEAD
 LOADS, LIVE LOADS, ROOF LOADS, FLOOD LOADS, SNOW LOADS,
 WIND LOADS AND SEISMIC LOADS AS PRESCRIBED BY THIS
 CODE. THE CONSTRUCTION OF BUILDINGS AND STRUCTURES IN
 ACCORDANCE WITH THE PROVISIONS OF THIS CODE SHALL
 RESULT IN A SYSTEM THAT PROVIDES A COMPLETE LOAD PATH
 THAT MEETS THE REQUIREMENTS FOR THE TRANSFER OF LOADS
 FROM THEIR POINT OF ORIGIN THROUGH THE LOAD-RESISTING
 ELEMENTS TO THE FOUNDATION. BUILDINGS AND STRUCTURES
 CONSTRUCTED AS PRESCRIBED BY THIS CODE ARE DEEMED TO
 COMPLY WITH THE REQUIREMENTS OF THIS SECTION.
  
 R301.2.1 WIND DESIGN CRITERIA.
 BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING
 THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED
 FROM FIGURE R301.2(4). THE STRUCTURAL PROVISIONS OF
 THIS CODE FOR WIND LOADS ARE NOT PERMITTED WHERE WIND
 DESIGN IS REQUIRED AS SPECIFIED IN SECTION R301.2.1.1.
 WHERE DIFFERENT CONSTRUCTION METHODS AND STRUCTURAL
 MATERIALS ARE USED FOR VARIOUS PORTIONS OF A BUILDING,
 THE APPLICABLE REQUIREMENTS OF THIS SECTION FOR EACH
 PORTION SHALL APPLY. WHERE NOT OTHERWISE SPECIFIED, THE
 WIND LOADS LISTED IN TABLE R301.2(2) ADJUSTED FOR
 HEIGHT AND EXPOSURE USING TABLE R301.2(3) SHALL BE USED
 TO DETERMINE DESIGN LOAD PERFORMANCE REQUIREMENTS FOR
 WALL COVERINGS, CURTAIN WALLS, ROOF COVERINGS, EXTERIOR
 WINDOWS, SKYLIGHTS AND EXTERIOR DOORS (OTHER THAN
 GARAGE DOORS).
  
  
  