| 2018-02-26 08:37:55 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 18020843 |
| | W. P. B. PERMIT: 16070715 |
| | ADD: 214 S. ROSEMARY AVE. |
| | CONT: MOSS & ASSOCIATES |
| | TEL: 954-868-5509 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 1ST REVIEW |
| | DATE: MON. FEB. 26/ 2018 |
| | ACTION: DENIED |
| | |
| | 1) THE SUBMITTED REPORT FROM WINGERTER LABORATORIES, |
| | INC. IS A COPY. THE SIGNATURE OF ROBERT H. SCHULER, P. |
| | E. IS A PHOTO COPY NOT AN ORIGINAL SIGNATURE AND SEAL. |
| | |
| | FL ADMIN CODE 61G15-23.002 ENGINEERS. EFFECTIVE DATE |
| | 05/06/2009. (2)(A) EVERY SHEET OF PLANS AND PRINTS |
| | WHICH MUST BE SEALED UNDER THE PROVISIONS OF CHAPTER |
| | 471, F.S., SHALL BE SEALED, SIGNED AND DATED BY THE |
| | PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE. |
| | |
| | 61G15-23.002(2)(B) FL. ADMIN. CODE. A COVER SHEET WITH |
| | LISTED PAGES OR INDEX SHEET FOR ENGINEERING |
| | SPECIFICATIONS MAY BE USED AND THAT SHEET MUST BE |
| | SIGNED IN RESPONSIBLE CHARGE OF THE PRODUCTION & |
| | PREPARATION OF EACH SECTION OF THE ENGINEERING |
| | SPECIFICATION WITH SUFFICIENT INFORMATION ON THE COVER |
| | SHEET OR INDEX LISTING HOW MANY PAGES ARE COVERED UNDER |
| | THE COVER SHEET OR INDEX SHEET. |
| | |