| Plan Review Notes For Permit 18020842 |
| Permit Number |
18020842 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-02-23 11:07:35 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THIS STRUCTURE IS LOCATED IN EXPOSURE CATEGORY B | | | WITH A VULT WIND SPEED OF 170 MPH. THE ROOFING SYSTEM | | | THAT WAS INDICATED DOES NOT MEET THE REQUIRED DESIGN | | | PRESSURES FOR THE PERIMETER AND CORNER ROOF AREAS. THE | | | TPO SYSTEM SPECIFIED ON PAGES 7 AND 8 OF NOA NO. | | | 14-0326.08 HAS A MAXIMUM DESIGN PRESSURE OF -45 PSF AND | | | CAN NOT BE INCREASED BY ENHANCED FASTENING PER | | | LIMITATION NUMBER 9 ON PAGE 22. | | | |
|