| Plan Review Notes For Permit 18020767 |
| Permit Number |
18020767 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-02-27 09:18:32 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #18020767 | | | 2/27/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE A REVISED M1 PLAN SHEET AND ANY OTHER | | | PLAN SHEETS AFFECTED BY THE CHANGE TO A LARGER FAN. | | | REVISE THE FAN SCHEDULE AND EXHAUST AND AIR BALANCE | | | CALCULATIONS ETC. ON THE M1 PLAN SHEET. | | | | | | 2) SUBMIT A FL. PRODUCT APPROVAL AND/OR A MIAMI-DADE | | | NOA FOR THE NEW ROOF CAP. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|