| Plan Review Notes For Permit 18020745 |
| Permit Number |
18020745 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-03-16 19:06:09 | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | FAC 61G20-3.001 FOR: | | | A) FLAT ROOF AS SHOWN ON PLANS. AND, CLEARLY MARK WHICH | | | APPROVED ASSEMBLY IS GOING TO BE INSTALLED TO VERIFY | | | COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301.1 | | | FBC-RESIDENTIAL. IF THE SELECTED ASSEMBLY DOESN'T MEET | | | THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN SIGNED | | | AND SEALED RAS 117 CALCULATIONS ARE REQUIRED. RAS 117 | | | CALCULATIONS ARE REQUIRED TO HAVE THE FLORIDA | | | ENGINEER'S SEAL AND ORIGINAL HANDWRITTEN SIGNATURE, | | | COPIES OR OTHER FACSIMILES ARE NOT ACCEPTABLE. FAC | | | 61G15 - 23.002 DIGITAL SIGNATURES ARE ONLY ACCEPTABLE | | | FOR ELECTRONICALLY TRANSMITTED PLANS AND DOCUMENTS. | | | |
|