| 2018-02-16 13:42:42 | ****PLAN REVIEW COMMENTS**** |
| | |
| | ART LANGE BUILDING PLANS EXAMINER |
| | |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH, FL 33402 |
| | |
| | 561-805-6718 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2017 6TH EDITION W/2010 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION / FRC FLORIDA RESIDENTIAL CODE |
| | 2017 6TH EDITION |
| | |
| | 1. PERMIT VALUE WAS ADJUSTED TO $7550.00 TO MATCH THE |
| | CONTACT PROVIDED. |
| | |
| | 2. : THE GAFGLAS FLEX PLY 6 USED HAS A LIMITATION #7. |
| | SEE GENERAL LIMITATION NUMBER 7. REVIEW THE PRODUCT |
| | APPROVAL LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED |
| | FOR ROOF ZONES 2 & 3. FASTENER DENSITIES SHALL BE |
| | INCREASED FOR BOTH INSULATION & THE BASE SHEET AS |
| | CALCULATED IN COMPLIANCE WITH ROOFING APPLICATION |
| | STANDARDS RAS 117. CALCULATION PREPARED, SIGNED AND |
| | SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR |
| | REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. |
| | |
| | |
| | WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM: |
| | |
| | HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2 |
| | 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION. |
| | WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED |
| | SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS |
| | READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE |
| | RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE |
| | FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR |
| | *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN |
| | THE PERMIT PACKAGE. |
| | |
| | A RESPONSE LETTER INDICATING HOW EACH ITEM WAS |
| | ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW. |
| | |