| Notes |
| Date |
Text |
| 2018-03-26 16:55:36 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | | | | | | | RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT | | | MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL | | | SPACE IS MORE THAN 6 FEET FROM A RECEPTACLE OUTLET. | | | PROVIDE CORRECTION. NEC 210.52; FBC RE3901.2.1 | | | | | | E3903.2 HABITABLE ROOMS. AT LEAST ONE WALL | | | SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED IN | | | EVERY HABITABLE ROOM AND BATHROOM. [210.70(A)(1)] |
|