Plan Review Notes
Plan Review Notes For Permit 18020667
Permit Number 18020667
Review Stop B
Sequence Number 1
Notes
Date Text
2018-03-06 14:03:15BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROPOSED WINDOWS AND SGC ARE NOT IMPACT RATED.
 2. PROVIDE SCHEDULE FOR OPENING PROTECTION.
 3. PROVIDE NOA FOR OPENING PROTECTION DEVICES.
 4. PROVIDE NOA FOR PROPOSED WALL PANELS.
 5. NOA FOR PROPOSED SGD IS NOT ON WINDOW AND DOOR
 SCHEDULE.
 6. PROVIDE LANDING AT EXTERIOR DOOR.
  
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS.
  
 R311.3 FLOORS AND LANDINGS AT EXTERIOR DOORS.
 THERE SHALL BE A LANDING OR FLOOR ON EACH SIDE OF EACH
 EXTERIOR DOOR. THE WIDTH OF EACH LANDING SHALL NOT BE
 LESS THAN THE DOOR SERVED. EVERY LANDING SHALL HAVE A
 MINIMUM DIMENSION OF 36 INCHES (914 MM) MEASURED IN THE
 DIRECTION OF TRAVEL. EXTERIOR LANDINGS SHALL BE
 PERMITTED TO HAVE A SLOPE NOT TO EXCEED 1/4 UNIT
 VERTICAL IN 12 UNITS HORIZONTAL (2-PERCENT).
  
 R311.3.1 FLOOR ELEVATIONS AT THE REQUIRED EGRESS DOORS.
 LANDINGS OR FINISHED FLOORS AT THE REQUIRED EGRESS DOOR
 SHALL NOT BE MORE THAN 11/2 INCHES (38 MM) LOWER THAN
 THE TOP OF THE THRESHOLD. EXCEPTION: THE LANDING OR
 FLOOR ON THE EXTERIOR SIDE SHALL NOT BE MORE THAN 73/4
 INCHES (196 MM) BELOW THE TOP OF THE THRESHOLD.
  
  
  
  