Plan Review Notes
Plan Review Notes For Permit 18020662
Permit Number 18020662
Review Stop M
Sequence Number 3
Notes
Date Text
2018-04-10 08:09:242ND REVIEW FBC-2014 MECHANICAL, WEST PALM BEACH
 AMENDMENTS TO THE FBC-14
 REVISION #18020662
 PERMIT #17120042
 4/10/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE ENGINEER OF RECORD WHO PREPARED THE ENERGY
 CALCULATIONS MUST PROVIDE HIS INK OR RAISED SEAL AND
 SIGNATURE ON THE CERTIFICATIONS PAGE #4 OF THE REVISED
 ENERGYGAUGE COMPLIANCE SUBMITTAL- SECTION C103.1.1.1.2
 FBC-14 ENERGY CONSERVATION. SEALS AND SIGNATURES ARE
 ALSO REQUIRED ON ANY AC CALCULATIONS FOR SYSTEMS
 GREATER THAN 15 TON- SECTION 105.3.1.2 WPB AMENDMENTS
 TO THE FBC.
  
 2) ADVISORY: COMMISSIONING OF THE MECHANICAL SYSTEMS IS
 REQUIRED PER SECTION C408.2 FBC-14 ENERGY CONSERVATION.
 SUBMIT A COMMISSIONING PLAN AS OUTLINED IN SECTION
 C408.2.1 AND DESCRIBED IN SECTIONS C403.2.2-
 C408.2.3.3. PLEASE NOTE THAT A COPY OF THE
 COMMISSIONING REPORT SHALL BE SUBMITTED TO THE
 OWNERSHIP, AND TO THE BUILDING DEPARTMENT FOR REVIEW AT
 FINAL INSPECTION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  