| Plan Review Notes For Permit 18020662 |
| Permit Number |
18020662 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2018-04-10 08:09:24 | 2ND REVIEW FBC-2014 MECHANICAL, WEST PALM BEACH | | | AMENDMENTS TO THE FBC-14 | | | REVISION #18020662 | | | PERMIT #17120042 | | | 4/10/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE ENGINEER OF RECORD WHO PREPARED THE ENERGY | | | CALCULATIONS MUST PROVIDE HIS INK OR RAISED SEAL AND | | | SIGNATURE ON THE CERTIFICATIONS PAGE #4 OF THE REVISED | | | ENERGYGAUGE COMPLIANCE SUBMITTAL- SECTION C103.1.1.1.2 | | | FBC-14 ENERGY CONSERVATION. SEALS AND SIGNATURES ARE | | | ALSO REQUIRED ON ANY AC CALCULATIONS FOR SYSTEMS | | | GREATER THAN 15 TON- SECTION 105.3.1.2 WPB AMENDMENTS | | | TO THE FBC. | | | | | | 2) ADVISORY: COMMISSIONING OF THE MECHANICAL SYSTEMS IS | | | REQUIRED PER SECTION C408.2 FBC-14 ENERGY CONSERVATION. | | | SUBMIT A COMMISSIONING PLAN AS OUTLINED IN SECTION | | | C408.2.1 AND DESCRIBED IN SECTIONS C403.2.2- | | | C408.2.3.3. PLEASE NOTE THAT A COPY OF THE | | | COMMISSIONING REPORT SHALL BE SUBMITTED TO THE | | | OWNERSHIP, AND TO THE BUILDING DEPARTMENT FOR REVIEW AT | | | FINAL INSPECTION. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|