| 2018-02-23 08:17:15 | 1ST REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION, | | | EXISTING BUILDING CODES | | | REVISION 318020662 | | | MASTER #17120042 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M2.1: PLEASE PROVIDE AN ENLARGED VIEW OF THE | | | NEW MDF ROOM TO HELP EXPEDITE THE REVIEW PROCESS. | | | | | | 2) M2.1: NOTE #6 IS CONFUSING. I AM NOT SEEING DUCTWORK | | | FROM THE EXISTING AC-1 AND AC-2 SYSTEMS. IT APPEARS THE | | | DUCTWORK IS FROM THE NEW LIEBERT SYSTEMS. | | | | | | 2) PROVIDE SIZING CALCULATIONS FOR THE NEW LIEBERT AND | | | MITSUBISHI SYSTEMS, AND PROVIDE EQUIPMENT SCHEDULES FOR | | | THE LIEBERT SYSTEMS. | | | | | | 3) PLEASE SHOW THE LOCATIONS OF AHU'S 8, 9, & 10. | | | | | | 4) SHEET M2.3: DUCT SMOKE DETECTORS REQUIRED IN THE | | | RETURN AIR SYSTEMS OF AHU'S 3, 4, 5, & 6. | | | | | | 5) PROVIDE COMPLETE WIND LOAD ENGINEERING FOR | | | INSTALLATION OF THE NEW LIEBERT UNITS, THE MITSUBISHI | | | CONDENSING UNITS, AND THE CHILLERS- SECTION 301.5. | | | | | | 6) REVISE THE ENERGY COMPLIANCE REPORT TO INCLUDE THE | | | NEW SYSTEMS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|