| Date |
Text |
| 2018-03-12 11:52:12 | 1) SUBMIT TWO SETS OF PLANS THAT CLEARLY REFLECT THE |
| | ENTIRE SCOPE OF WORK TO BE DONE. SUBMIT TWO COPIES OF |
| | AN EXISTING FLOOR PLAN AND ALSO A PROPOSED FLOOR PLAN. |
| | WPB AMEND. TO FBC SEC. 107.1, 107.2.1. |
| | 2) COMPLY WITH WPB AMEND. TO FBC 107.3.5 FOR MINIMUM |
| | PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | 3) THE PLANS DO NOT INDICATE TO WHAT CODE THEY WERE |
| | DEVELOPED. THE PLANS SHALL COMPLY WITH THE 2017 |
| | FBC-EXISTING BUILDING CODE AND THE OTHER APPLICABLE |
| | VOLUMES OF THE 2017 FBC. THE LEVEL OF ALTERATION SHALL |
| | BE NOTED ON THE PLANS PER SEC. 301.1 OF THE 2017 |
| | FBC-EXISTING BUILDING CODE. |
| | 4) 2017 FBC-EXISTING BUILDING CODE SEC. 301.1 - THE |
| | ALTERATION OF ALL EXISTING BUILDINGS SHALL COMPLY WITH |
| | ONE OF THE METHODS LISTED IN SECS.301.1.1 THROUGH |
| | 301.1.3 AS SELECTED BY THE APPLICANT. |
| | 5) SUBMIT PLANS/DETAILS SHOWING HOW COMPLIANCE WITH THE |
| | 2017 FBC-ACCESSIBILITY CODE WILL BE ACCOMPLISHED. |
| | 6) THE HEIGHT OF THE LUNCH ROOM CABINET COUNTERTOP AND |
| | SINK SHALL COMPLY WITH THE 2017 FBC-ACCESSIBILITY SECS. |
| | 212 & 606. |
| | 7) ONE OF THE SUBMITTED PLAN SHEETS IS DONE IN PENCIL. |
| | PLANS DONE IN PENCIL ARE NOT AN ACCEPTED FORMAT. WPB |
| | AMEND. TO FBC SEC.107.1. |
| | 8) THE NOTE FOR THE SCOPE OF PLUMBING WORK FOR THE |
| | LUNCH ROOM ON THE SECOND FLOOR IS INCOMPLETE AND IS |
| | VAGUE. CLARIFY THE COMPLETE SCOPE OF PLUMBING WORK TO |
| | BE DONE. WPB AMEND. TO FBC SEC. 10.2.1. |
| | 9) THE PLANS FOR THE 2ND FLOOR BATHROOM ALTERATION |
| | SHALL SHOW THE LOCATION OF ALL EXISTING PLUMBING |
| | FIXTURES AND ANY NEW LOCATIONS OF THE FIXTURES, |
| | LOCATIONS OF STALL PARTITIONS, THE LENGTH AND WIDTH |
| | DIMENSIONS OF ALL PLUMBING FIXTURE STALLS, ETC. |
| | 10) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE TYPE |
| | OF PLUMBING FIXTURES TO BE INSTALLED. NEW FIXTURES |
| | SHALL COMPLY WITH THE 2017 FBC- PLUMBING SEC. 604.4 FOR |
| | MAXIMUM WATER FLOW AND CONSUMPTION. |
| | 11) NEW FAUCETS SHALL COMPLY WITH 2017 FBC-PLUMBING |
| | SEC.605.2.1. FOR LEAD CONTENT AND SHALL COMPLY WITH NSF |
| | 372. |
| | |
| | NOTE: BECAUSE OF THE LACK OF REQUIRED INFORMATION ON |
| | THE SUBMITTED DRAWINGS A COMPREHENSIVE PLAN REVIEW |
| | COULD NOT BE DONE. RE- REVIEW OF CORRECTED DOCUMENTS |
| | MAY RESULT IN ADDITIONAL PLAN REVIEW COMMENTS BEING |
| | GENERATED. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |