| Plan Review Notes For Permit 18020636 |
| Permit Number |
18020636 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-03-09 17:03:01 | 03/09/2018 PLUMBING 2ND REVIEW**DENIED** | | | | | | THE BUILDING WAS BUILT USING THE FAIR HOUSING DESIGN | | | MANUAL IN 2006 | | | | | | 1) YOU WILL NOT BE ABLE TO REMOVE 1 SINK BASE TO | | | INSTALL A DOUBLE VANITY AND COMPLY WITH THE REQUIRED | | | CLEAR FLOOR SPACE FOR A SIDE APPROACH OF 30" X 48". THE | | | SINK MUST REMAIN CENTERED AT A MIN 24".(FHA DESIGN | | | MANUAL 7.48). IT ALSO DOES NOT COMPLY WITH FBC P | | | 405.3.1 AS YOUR SHOWING THE CENTER OF SINK @ 12" WHEN | | | 15" IS AND ALWAYS HAS BEEN THE MIN CODE. | | | | | | 2) THE COUNTER TOP HEIGHT IS NOT EXISTING AS EXISTING | | | AND FHA DESIGN MANUAL IS MAX 34" TO TOP OF RIM. ( FHA | | | DESIGN MANUAL 7.52) | | | | | | | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS | | | |
|