| Plan Review Notes For Permit 18020610 |
| Permit Number |
18020610 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-02-20 15:51:13 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT #18020610 | | | 2/20/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) M-1.0: EXHAUST REQUIRED FOR THE LOCKER ROOM- TABLE | | | 403.1.1. | | | | | | 2) M-1.0: VERIFY THAT THE 36"X48" ACCESS PANEL IS LARGE | | | ENOUGH TO REMOVE AND REPLACE THE AIR HANDLER- SECTION | | | 306.1. | | | | | | 3) M-2.0: CORRECT NOTE #13 WHICH IS REFERENCING THE | | | OUTDATED 2014 FLORIDA ENERGY CONSERVATION CODE. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|