| 2018-02-20 13:36:40 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL WHICH INCLUDES INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| | ESTIMATED VALUES ARE NOT ACCEPTABLE DUE TO LABELING |
| | REQUIREMENT OF NEC 110.24. THIS CAN BE PROVIDED AS A |
| | DEFERRED SUBMITTAL PRIOR TO INSPECTION IF DESIRED. IF |
| | SO, PROVIDE NOTE TO THAT AFFECT. NEC 110.9, 110.10 |
| | 2. PROVIDE NOTE TO INDICATE MARKING OF HIGH-LEG PER |
| | CODE. NEC 110.15 |
| | 3. RECEPTACLE CONTROL DETAILED ON PLAN DOES NOT MEET |
| | CODE REQUIREMENTS. PROVIDE RECEPTACLE CONTROL REQUIRED |
| | BY ASHREA 90.1: 8.4.2. PER THIS REQUIREMENT, THE |
| | FOLLOWING SHALL BE AUTOMATICALLY CONTROLLED: 1) AT |
| | LEAST 50% OF ALL 125-VOLT, 15 AND 20 AMP RECEPTACLES, |
| | IN ALL PRIVATE OFFICES, CONFERENCE ROOMS, ROOMS USED |
| | PRIMARILY FOR PRINTING AND/OR COPYING FUNCTIONS, BREAK |
| | ROOMS, CLASSROOMS, AND INDIVIDUAL WORKSTATIONS. 2) AT |
| | LEASE 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR |
| | MODULAR FURNITURE NOT SHOWN ON THE CONSTRUCTION |
| | DOCUMENTS. FBC EC C405.6.1 |
| | 4. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. SHOW ON PLAN. NEC 250.94 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |
| | |