| Plan Review Notes For Permit 18020559 |
| Permit Number |
18020559 |
|
| Review Stop |
P |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2018-07-20 15:25:15 | 1) SHT. A -1 - PLUMBING RISERS - SUBMIT TWO COPIES OF A | | | CODE COMPLIANT SANITARY RISER DIAGRAM. THERE ARE TOO | | | MANY CODE VIOLATIONS TO LIST. WPB AMEND.TO FBC SEC. | | | 107.2.1. | | | 2) SIZE ALL SECTIONS OF THE DRAINAGE LINES AND VENT | | | LINES ON THE SANITARY RISER DIAGRAMS WHEN TEY ARE | | | REVISED. | | | 3) THE PLANS SHOW A MASTER BATHROOM AND AN EXISTING | | | BATHROOM BUT THE SANITARY RISER DIAGRAMS ARE FOR A | | | MASTER BATH AND ALSO A NEW STORAGE BATH. CLARIFY. | | | 4) SHT. A-2 - ADDITION ROOF PLAN - SUBMIT A DETAIL OF | | | THE ROOF SCUPPER. WPB AMEND. TO FBC SEC. 107.2.1. | | | 5) SHT. A-4 IS MISSING FROM ONE SET OF PLANS. | | | 6) THE ROOF PLAN REFERS TO TABLE 1106.3 OF THE FLORIDA | | | PLUMBING CODE. THIS TABLE IS FOR VERTICAL LEADER | | | SIZING, NOT SCUPPERS.CLARIFY. | | | 7) SHOW REQUIREMENTS FOR SECONDARY (EMERGENCY) ROOF | | | DRAINAGE PER 2017 FBC-PLUMBING SEC. 1108.1. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|