| 2018-07-20 10:14:25 | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF |
| | SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, |
| | WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY |
| | SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW |
| | INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230, |
| | 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1, |
| | E3609.3; FBC 107.2.1 (NOT PROVIDED ON SHEET A-2 AS |
| | MENTIONED IN RESPONSE.) |
| | 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY |
| | WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC RE |
| | E3706.2, E3902 (NOT PROVIDED ON SHEET A-2 AS MENTIONED |
| | IN RESPONSE.) |
| | 3. CORRECTED. |
| | 4. CORRECTED. |
| | 5. CORRECTED. |
| | 6. CORRECTED. |
| | 7. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE |
| | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| | IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2 |
| | (NOT PROVIDED ON SHEET A-2 AS MENTIONED IN RESPONSE.) |
| | 8. CORRECTED. |
| | 9. CORRECTED. |
| | 10. CORRECTED. |
| | 11. PROVIDE FULL FLOOR PLAN SHOWING SMOKE ALARMS IN |
| | EACH LOCATION REQUIRED PER CODE. SHOW ON PLAN ALL |
| | EXISTING ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, |
| | SHOW AS NEW INSTALLATIONS. SMOKE ALARMS MUST BE |
| | INSTALLED AT LEAST 3 FEET FROM BATHROOM DOOR, 3 FEET |
| | FROM CEILING FANS, AND 3 FEET FROM ANY MECHANICAL DUCT. |
| | PROVIDE CORRECTIONS. FBC RE R314.3(4), NFPA |
| | 72:29.8.3.4; FBC R314.3, FBC 107.2.1 (NOT PROVIDED AS |
| | MENTIONED IN RESPONSE.) |
| | 12. CORRECTED. |
| | 13. CORRECTED. |
| | 14. CORRECTED. |
| | 15. FEE ADDED. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | PHIL PETTY |
| | CHIEF ELECTRICAL INSPECTOR |
| | 561-805-6742 |
| | [email protected] |
| | |