| 2018-04-11 09:03:49 | NO CHANGE TO PLAN |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF |
| | SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, |
| | WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY |
| | SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW |
| | INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230, |
| | 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1, |
| | E3609.3; FBC 107.2.1 |
| | 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY |
| | WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC RE |
| | E3706.2, E3902 |
| | 3. PROVIDE AFCI PROTECTION PER CODE: ?BRANCH CIRCUITS |
| | THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE |
| | OUTLETS INSTALLED IN KITCHENS, FAMILY ROOMS, DINING |
| | ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS, |
| | BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, |
| | HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS |
| | SHALL BE AFCI PROTECTED.? PROVIDE CORRECTION. NEC |
| | 210.12; FBC RE E3902.16 |
| | 4. RECEPTACLES IN STORAGE AREAS REQUIRE GFCI |
| | PROTECTION. PROVIDE CORRECTION. NEC 210.8; FBC RE |
| | E3902.2 |
| | 5. LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE |
| | SUITABLE FOR DAMP LOCATIONS. PROVIDE CORRECTION. NEC |
| | 410.10(D); FBC RE E4003.11 |
| | 6. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| | FBC EC R404.1 |
| | 7. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE |
| | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| | IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2 |
| | 8. FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED |
| | GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL |
| | SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED ON |
| | THE EXTERIOR SIDE OF OUTDOOR ENTRANCES/EXITS WITH GRADE |
| | LEVEL ACCESS. PROVIDE CORRECTION. NEC 210.70(A)(2)(B), |
| | FBC RE E3903.3 |
| | 9. PROVIDE BLOCK NOTE THAT POOL WILL BE UNDER SEPARATE |
| | PERMIT. FBC 107.2.1, 105.1 |
| | 10. A BUILDING OR OTHER STRUCTURE THAT IS SERVED BY A |
| | BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF A SERVICE |
| | DISCONNECTING MEANS SHALL BE SUPPLIED BY ONLY ONE |
| | FEEDER OR BRANCH CIRCUIT. PROVIDE DETAILS. NEC 225.30 |
| | 11. PROVIDE FULL FLOOR PLAN SHOWING SMOKE ALARMS IN |
| | EACH LOCATION REQUIRED PER CODE. SHOW ON PLAN ALL |
| | EXISTING ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, |
| | SHOW AS NEW INSTALLATIONS. SMOKE ALARMS MUST BE |
| | INSTALLED AT LEAST 3 FEET FROM BATHROOM DOOR, 3 FEET |
| | FROM CEILING FANS, AND 3 FEET FROM ANY MECHANICAL DUCT. |
| | PROVIDE CORRECTIONS. FBC RE R314.3(4), NFPA |
| | 72:29.8.3.4; FBC R314.3, FBC 107.2.1 |
| | 12. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A |
| | NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14 |
| | 13. A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE |
| | PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH |
| | CIRCUITS SHALL HAVE NO OTHER OUTLETS. PROVIDE PER CODE. |
| | NEC 210.11(C)(3) , FBC RE E3703.4 |
| | 14. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C |
| | EQUIPMENT PER CODE. NEC 210.63; FBC RE E3901.12 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |