Plan Review Notes
Plan Review Notes For Permit 18020555
Permit Number 18020555
Review Stop P
Sequence Number 1
Notes
Date Text
2018-02-20 11:28:291ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. TUB STILL SHOWN ON SANITARY ISOMETRIC CHANGE TO
 MATCH SHOWERS ON FLOOR PLAN. PER WPB AMEND TO FBC
 107.2.1
  
 2. WASHING MACHINE ON FIRST AND SECOND FLOOR NOT
 VENTED-SHOW STAND PIPE AND P-TRAP. PER FBC RES
 P3101.2.1
  
 3. CLEAN OUT REQUIRED AT THE BASE OF THE 4" SOIL STACK.
 PER FBC RES P3005.2.6
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  