2018-02-15 06:35:14DENIED
 1. A SITE PLAN DEPICTING THE GENERAL LOCATION OF THE
 PROPOSED BACKFLOW PREVENTION DEVICE. YOU CAN DO A
 SKETCH OR USE PROPERTY APPRAISER WEB SITE HTTP://WWW.CO
 .PALM-BEACH.FL.US/PAPA/ASPS/PROPERTYDETAIL/STRUCTURALDE
 TAIL.ASPX?ENTITY_ID=74434334110020151&OWNER_NAME=ORTIZ+
 RUIZ+ADRIAN+C . TELL US WHERE YOUR WATER METER IS AND
 WHERE THE BACKFLOW WILL BE PLACED.
 2. TWO COPIES OF THE MANUFACTURER?S SPECIFICATIONS FOR
 THE BACKFLOW PREVENTER. THE MAKE, MODEL, AND SIZE OF
 THE DEVICE SHALL BE LISTED IN THE DESCRIPTION OF WORK
 SECTION ON THE PERMIT APPLICATION.
 3. DOCUMENTATION THAT THE PROPOSED DEVICE IS LEAD-FREE.
 4. DOCUMENTATION THAT THE PROPOSED BACKFLOW DEVICE IS
 ON THE APPROVED DEVICE LIST PUBLISHED BY THE UNIVERSITY
 OF SOUTHERN CALIFORNIA (USC). PLEASE CONTACT DEPARTMENT
 OF PUBLIC UTILITY FIELD CUSTOMER SERVICE AT
 561-822-2240 FOR DOCUMENTED CONFIRMATION THAT THE
 PROPOSED BACKFLOW PREVENTION DEVICE COMPLIES WITH CITY
 REQUIREMENTS.
 5. THE CITY OF WEST PALM BEACH UTILITIES REQUIRES THE
 WATER SUPPLY PIPING BETWEEN THE METER AND THE BACKFLOW
 PREVENTION DEVICE TO BE A MINIMUM OF TYPE K COPPER. PVC
 PIPING IS NOT PERMITTED. EXISTING WATER SUPPLIES NOT
 MEETING THESE CRITERIA MUST BE UPGRADED. PLEASE CALL
 561- 822-2240 FOR FURTHER INFORMATION.
 6. ALL DEVICES MUST BE TESTED AND CERTIFIED BY THE CITY
 OF WEST PALM BEACH UTILITIES DEPARTMENT PRIOR TO THE
 FINAL INSPECTIONS BY THE BUILDING DEPARTMENT. PLEASE
 CONTACT THE CITY OF WEST PALM BEACH PUBLIC UTILITIES
 CENTRAL OPERATIONS AT 561-822-2210 TO ARRANGE FOR THE
 UTILITIES DEPARTMENT TO CERTIFY THE DEVICE.
  