Plan Review Notes
Plan Review Notes For Permit 18020521
Permit Number 18020521
Review Stop B
Sequence Number 3
Notes
Date Text
2018-08-17 19:13:55CHANGE OF OCCUPANCY, THIRD BUILDING REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017).
  
  
 ORIGINAL COMMENT:
 1-CHANGE OF OCCUPANCY SHALL COMPLY WITH THE ENERGY
 CONSERVATION CODE.
  
 RESPONSE:
 (A) ENERGY CALCULATIONS SUBMITTED WERE CHANGED. THE NEW
 FORM NEEDS TO BE SIGNED AND SEALED BY THE ARCHITECT OF
 RECORD ALSO AS REQUIRED BY SEC. C103.1.1.1.2 FBC-ENERGY
 CONSERVATION. NOTE: ENVELOPE INFORMATION SHOWN ON THE
 ENERGY CALCULATIONS AND PLANS DON'T MATCH. SEE TYPE OF
 WALLS FRAMING, CEILING INFORMATION INCLUDING
 INSULATION, ETC. CLEARLY ARCHITECT AND MECHANICAL
 ENGINEER TO COORDINATE INFORMATION TO AVOID
 CONFLICTS/DELAYS.
  
 (B)THE BOXES FROM THE MANDATORY REQUIREMENTS THAT ARE
 ASSIGNED TO THE PLANS REVIEWER AND INSPECTORS WERE
 CHECKED. ENGINEER CAN NOT CHECK THESE BOXES. REVISE AS
 REQUIRED.
  
 (C) THE OWNER OR OWNER'S AUTHORIZED AGENT NEED TO
 CERTIFY THE FORM AFTER CALCULATIONS ARE REVISED. SEC.
 C103.1.1.2 FBC-ENERGY CONSERVATION.
  
 ORIGINAL COMMENT:
 2-IMPACT FEES
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.
  
 ORIGINAL COMMENT:
 3- LIFE SAFETY PLAN NOT PROVIDED.
  
 RESPONSE:
 LIFE SAFETY PLAN SHEET A-3 SUBMITTED. :
 (A)CLARIFY WHY PROVIDING THE "MEANS OF EGRESS"
 INFORMATION SHOWN IN THE LIFE SAFETY PLAN. IT DOESN'T
 SEEM TO APPLY TO THIS PROJECT. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 (B)THIS IS A MIXED OCCUPANCY. FACTORY AND BUSINESS
 (OFFICE/FOYER/RECEPTION AREA). PROVIDE OCCUPANCY LOAD
 CALCULATIONS FOR THE FACTORY AREA AND LOAD CALCULATIONS
 FOR THE OFFICE AREA. THESE ARE TWO DIFFERENT
 CALCULATION'S. SEE TABLE 1004.1.2 FBC AND REVISE AS
 REQUIRED.
  
 (C) INFORMATION SHOWN AT THE BOTTOM OF SHEET A-3 IS
 INCORRECT. THERE IS NOT COMMON PATH OF EGRESS TABLE
 1014.3 AND NUMBER OF EXITS REQUIRED TABLE 1018 IN THE
 2017 FBC. SEE CHAPTER 10 OF FBC-2017 AND REVISE AS
 REQUIRED.
  
 (D)FIRE EXTINGUISHER INFORMATION SPECIFIED IN THE
 SYMBOL LEGEND DOESN'T MATCH FIRE EXTINGUISHER
 INFORMATION SHOWN AT THE BOTTOM OF SHEET A-3 AND
 INFORMATION SHOWN ON THE FLOOR PLAN. REVISE AS
 REQUIRED. SEC. 906 FBC.
  
 (E) THE SWING DIRECTION OF THE EXIT DOOR LEADING TO THE
 FOYER AREA FROM THE FACTORY AREA DOESN'T MATCH SWING
 DIRECTION SHOWN ON THE FLOOR PLAN ON SHEET A-1. REVISE
 AS REQUIRED TO MATCH. SEC. 1010.1.2.1 FBC.
  
 ORIGINAL COMMENT:
 4- EXTERIOR WALLS REQUIRE A FIRE RESISTANCE RATING OF 2
 HOURS AS REQUIRED BY SEC. 1012.6 FBC-EXISTING BUILDING
 AND TABLE 602 FBC. PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS SHOWING COMPLIANCE WITH THE 2 HOUR FIRE
 RESISTANCE RATING.
 NOTE: CALCULATED FIRE RESISTANCE SEC. 722 FBC MAY BE
 USED BASED ON THE MATERIALS USED.
  
 RESPONSE:
 CONCRETE BLOCK DETAIL 1/A-3 ON SHEET A-2 IS FOR "NON
 RATED EXISTING MASONRY WALL". THE CHANGE OF OCCUPANCY
 FROM BUSINESS TO FACTORY REQUIRES A 2 HOUR FIRE
 RESISTANCE RATING OF THE WALL. PROVIDE COMPLETE DETAILS
 AND SPECIFICATIONS FOR 2 HR FIRE RATED ASSEMBLY. NOTES:
 (1)ASSEMBLY SHALL BE RATED FOR EXPOSURE TO FIRE FROM
 BOTH SIDES.
  
 ORIGINAL COMMENT:
 5- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 INTERIOR PARTITIONS. SPECIFY ALL FRAMING MEMBERS ,
 SPACING, CONNECTORS, ETC. SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 INTERIOR PARTITIONS ON SHEET A-2 NEED TO BE COORDINATED
 WITH FLOOR PLAN ON SHEET A-1. UL DES#U305 SPECIFIED ON
 DETAIL 2/A-3 IS NOT FOR 2 HOUR RATED PARTITION. ALSO
 WALL TYPES (WOOD OR METAL?) NEED TO BE COORDINATED WITH
 WALL TYPES SPECIFIED ON FLOOR KEY NOTES ON SHEET A-1.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 NEW COMMENTS:
 6- SHEET A-1:
 A) THE FLOOR KEY NOTES AND THE NOTES KEYED ON THE FLOOR
 PLAN NEED TO BE COORDINATED. FOR EXAMPLE KEY NOTE # 18
 IS FOR NEW WALK IN COOLER BUT IT IS POINTING TO A FIRE
 EXTINGUISHER. CORRELATE ALL KEY NOTES TO AVOID
 CONFLICTS/DELAYS. SEC. 107.2.1 CITY AMENDMENTS.
  
 B)REVISE PROJECT DATA: THE AREA ALLOWED FOR AN F-1
 OCCUPANCY FOR A TYPE VB BUILDING IS 8,500 NOT 13,000.
 SEE TABLE 506.2 FBC AND REVISE AS REQUIRED.
  
 C) THE DOOR SCHEDULE AND DOORS KEYED ON THE FLOOR PLAN
 DON'T MATCH. ALSO, COORDINATE WITH THE FLOOR KEY NOTES.
 CORRELATE ALL THE INFORMATION TO AVOID
 CONFLICTS/DELAYS. SEC. 107.2.1 CITY AMENDMENTS.
  
 D)PROVIDE DIMENSIONS FOR REAR TOILET ROOM. SEC. 603
 FBC-ACCESSIBILITY.
  
 E) FLOOR PLAN IS NOT CLEAR. THERE IS A PARTITION
 OVERLAPPING THE FOYER AND OFFICE AREA. REVISE AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 F) REVISE THE WIND DESIGN NOTES:
 (1)THE ASCE-7 THAT IS REFERENCED IN THE 2017 FBC IS THE
 2010 EDITION NOT 02. REVISE AS REQUIRED. CHAPTER 553
 F.S.
 (2) THE WIND EXPOSURE IS "C" NOT "B". SEE STRUCTURAL
 DRAWINGS AND REVISE AS REQUIRED. SEC. 1609.4 FBC.
  
 G) LAST NOTE AT THE BOTTOM RIGHT OF SHEET A-1
 REFERENCES "THIS RESIDENCE". THIS DOESN'T APPLY TO THIS
 PROJECT. REVISE AS REQUIRED. SEC. 301.1 FBC.
  
 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
  
 A) ENTRY DOOR. NOTE: PRODUCT APPROVAL TO INCLUDE
 INSTALLATION TO STEEL FRAMED WALL AS SPECIFIED ON
 PLANS.
  
 B) SLIDING WINDOW. NOTE: PRODUCT APPROVAL TO INCLUDE
 INSTALLATION TO STEEL FRAMED WALL AS SPECIFIED ON
 PLANS.
  
 8- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
  
 NOTE: ADDITIONAL COMMENTS MAY ARISE BASED ON THE
 INFORMATION SUBMITTED BY THE DESIGN PROFESSIONAL TO
 ADDRESS ALL THE COMMENTS.
  
  
  
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW
  
  
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS.
  
  