Plan Review Notes
Plan Review Notes For Permit 18020521
Permit Number 18020521
Review Stop P
Sequence Number 2
Notes
Date Text
2018-05-02 10:07:241ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE MOP SINK SHALL DISCHARGE THRU THE GREASE TRAP
 YOUR SIZING CALCULATION INCLUDE THE MOP SINK BUT THE
 SANITARY ISOMETRIC DOES NOT SHOW IT CONNECTING TO THE
 GREASE TRAP. PER FBC PL 1003.1
  
 2. SHT. S-3 THE FLOOR PLAN OF THE BATHROOM DOES NOT
 SHOW THE NEW EXTENDED WALLS PLEASE PROVIDE A FLOOR PLAN
 OF THE BATHROOM SHOWING THE NEW EXTENDED WALLS AND THE
 CLEAR FLOOR SPACE FOR THE TOILET AND LAVATORY.
 PER FBC ACC 604.3.1, 606.2
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  