| Plan Review Notes For Permit 18020521 |
| Permit Number |
18020521 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-05-02 13:30:51 | 2ND REVIEW FBC-2017 MECHANICAL | | | PERMIT #18020521 | | | 5/2/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE EXHAUST FANS IN THE WALL THAT ARE LABELED AS | | | EXISTING MAY HAVE BEEN INSTALLED WITHOUT A PERMIT, AND | | | ALSO MAY NOT BE ALLOWED BY CODE DUE TO THEIR RESPECTIVE | | | CLEARANCE DISTANCES TO THE ADJOINING PROPERTY LINES. | | | THE MECHANICAL APPROVAL FOR THE PROPOSED PLANS ARE ON | | | HOLD PENDING RESOLUTION OF THE ISSUE. PLEASE SEE THE | | | BUILDING AND PLUMBING RVIEW COMMENTS. | | | | | | 2) THE COMBUSTION AIR CALCULATIONS USING "FAN ASSISTED | | | APPLIANCES" DO NOT APPEAR APPLICAGBLE TO THE OVENS | | | WHICH DO NOT APPEAR TO HAVE FANS. PLEASE PROVIDE | | | FURTHER INFORMATION IN THE FORM OF A PRODUCT DATA SHEET | | | FOR THE OVENS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|