Plan Review Notes
Plan Review Notes For Permit 18020521
Permit Number 18020521
Review Stop B
Sequence Number 2
Notes
Date Text
2018-05-08 17:44:52CHANGE OF OCCUPANCY, SECOND BUILDING REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017).
  
  
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW
  
  
  
 1. COMPLIED.
  
 2. ORIGINAL COMMENT:
 PROVIDE THE BUILDING CONSTRUCTION TYPE AND IF IT IS
 SPRINKLERED OR UNSPRINKLERED FBC 602, FBC 107.2.1
  
 RESPONSE:
 REPEAT COMMENT (SECOND TIME). TYPE OF CONSTRUCTION
 SPECIFIED ON SHEET S-1 IS IN CORRECT. THERE IS NOT
 CONSTRUCTION TYPE VI. SEE SEC. 602 FBC-BUILDING AND
 REVISE AS REQUIRED. ALSO, CLEARLY SPECIFY IF SPECIFIED
 CONSTRUCTION TYPE IS A OR B. AND, SPECIFY IF THE
 BUILDING IS SPRINKLERED OR NOT.
  
 3- ORIGINAL COMMENT:
 THE PREVIOUS OCCUPANCY ON RECORD IS FOR AUTO SALES AND
 SERVICE. THIS IS A CHANGE OF OCCUPANCY. SHOW ON THE
 PLANS THE OCCUPANCY CLASSIFICATION AND USE. SEE ALSO
 FBC 302 AND 306.2.
  
 A) EXISTING BUILDING CODE 506.1 SCOPE.
 CHANGE OF OCCUPANCY PROVISIONS APPLY WHERE THE ACTIVITY
 IS CLASSIFIED AS A CHANGE OF OCCUPANCY AS DEFINED IN
 CHAPTER 2.
  
 CHANGE OF OCCUPANCY A CHANGE IN THE USE OF THE BUILDING
 OR A PORTION OF A BUILDING. A CHANGE OF OCCUPANCY SHALL
 INCLUDE ANY CHANGE OF OCCUPANCY CLASSIFICATION, ANY
 CHANGE FROM ONE GROUP TO ANOTHER GROUP WITHIN AN
 OCCUPANCY CLASSIFICATION OR ANY CHANGE IN USE WITHIN A
 GROUP FOR A SPECIFIC OCCUPANCY CLASSIFICATION.
  
 EXISTING BUILDING CODE 506.2 APPLICATION. CHANGES OF
 OCCUPANCY SHALL COMPLY WITH THE PROVISIONS OF CHAPTER
 10.
 THE PROVISIONS OF THE FLORIDA BUILDING CODE, EXISTING
 BUILDING SHALL APPLY TO THE REPAIR, ALTERATION, CHANGE
 OF OCCUPANCY, ADDITION AND RELOCATION OF EXISTING
 BUILDINGS.
  
 RESPONSE:
 REPEAT COMMENT (SECOND TIME). PLANS DON'T PROVIDE
 INFORMATION REGARDING THE CHANGE OF OCCUPANCY. NEED TO
 BE CLEAR ON THE PROPOSED USE. PLAN REVIEW CAN NOT BE
 PROPERLY PERFORMED IF THE PROPOSED USE IS NOT CLEARLY
 DEFINED. PLANS SHOW EVERYTHING AS EXISTING. THERE ARE
 NO CITY RECORDS REGARDING THE CHANGE OF USE. EVERYTHING
 NEEDS TO COMPLY FOR THE PROPOSED USE. PLANS NEED TO BE
 CLEAR ON THE PROPOSED USE AND NEED TO SHOW EVERYTHING
 AS PROPOSED.
  
  
 B)ORIGINAL COMMENT:
 CHANGE OF OCCUPANCY SHALL COMPLY WITH THE ENERGY
 CONSERVATION CODE.
  
 RESPONSE:
 ENERGY CALCULATIONS FORM C402-2017 SUBMITTED:
 (1)THE OWNER OR OWNER'S AUTHORIZED AGENT NEED TO
 CERTIFY AT THE BOTTOM OF FORM AS REQUIRED BY SEC.
 C103.1.1.2 FBC-ENERGY CONSERVATION.
  
 (2) PROVIDE COMPLETE INFORMATION ON TOP OF FORM.
 SPECIFY OCCUPANCY TYPE; PROVIDE BUILDER'S NAME; PROVIDE
 OWNER'S NAME.
  
  
 4- FRAMING.
  
 ORIGINAL COMMENT:
 A) HEADER AND JACK STUDS NOT SHOWN. SHOW COMPLIANCE
 WITH TABLE 2308.4.1.1(1)
  
 RESPONSE:
 REPEAT COMMENT (SECOND TIME). JACK STUDS ARE NOT SHOWN.
 ONLY THE KING STUDS ARE SHOWN. CRIPPLE STUDS SPACING
 SHOWN ABOVE HEADER AND BELOW WINDOW SILL ARE NOT DRAWN
 TO SCALE. CLARIFY HEADER SIZE (5)2X5 ?. FRAMING OF NEW
 2X8 STUDS TO THE EXISTING KNEE WALL IS NOT CLEAR. HOW
 ARE THE 2X8 STUDS ATTACHED TO THE EXISTING KNEE WALL?.
 WHAT IS THE KNEE WALL CONSTRUCTED OF?. SEC. 1609.1
 FBC-BUILDING.
  
 B) COMPLIED.
  
 5- COMPLIED.
  
 6. ORIGINAL COMMENT:
 PROVIDE PRODUCT APPROVALS FOR AIR INTAKE VENT.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 RESPONSE:
 PROVIDE 2 COPIES. ONLY ONE WAS PROVIDED. AND, NEED THE
 APPROVAL OF THE DESIGNER OF RECORD. NOTE: ENGINEER TO
 PLEASE PLACE THE REVIEW STAMP ON THE FRONT OF THE COVER
 PAGE OR ANY OTHER FRONT PAGE NOT ON THE BACK. THIS IS
 REQUIRED FOR PROPER RECORDS RETENTION. STAMPS ON THE
 BACK OF THE PAGE DON'T GET SCANNED.
  
 7. COMPLIED.
  
 8. ORIGINAL COMMENT:
 PERMIT VALUE IS TOO LOW.
  
 RESPONSE:
 VALUE WAS UPDATED TO $42,000 STILL TOO LOW. VALUE TO
 INCLUDE ALL LABOR, MATERIALS, EQUIPMENT (EVEN IF PLANS
 CALL FOR EXISTING EQUIPMENT. IT WAS NEVER PERMITTED),
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONAL FEES.
  
 9. IMPACT FEES
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.
  
 10. OTHER ITEMS NOT PROVIDE IN THE PLAN.
 ORIGINAL COMMENT:
 A. COMPLIANCE WITH FLORIDA ACCESSIBILITY CODE.
  
 RESPONSE:
 MAIN ENTRANCE TO THE BUILDING AND ENTRY AREA RESTROOM
 NEED TO COMPLY WITH THE FLORIDA ACCESSIBILITY CODE
 ALSO. DOORS NEED TO COMPLY WITH THE MANEUVERING
 REQUIREMENTS AND RESTROOMS NEED TO COMPLY WITH DOORS
 MANEUVERING AND FIXTURES CLEARANCES, ETC.
 SEC. 202.4 FBC ACCESSIBILITY. SEC. 404 FBC
 ACCESSIBILITY. SEC. 603 AND 604 FBC ACCESSIBILITY.
 NOTE; THERE ARE NO CITY RECORDS FOR ANY WORK DONE BY
 THE ENTRY AREA. THE LAST PERMIT (ELECTRICAL PERMIT
 03061436 TO INSTALL 2 EMERGENCY LIGHTS) SHOWING THE
 INTERIOR LAYOUT ONLY SHOWS AN OFFICE AT THE FRONT LEFT
 SIDE OF THE BUILDING. IT IS UNKNOWN WHEN THE ENTRY AREA
 WAS BUILT.
  
  
 ORIGINAL COMMENT:
 B. LIFE SAFETY PLAN NOT PROVIDED.
  
 RESPONSE:
 REPEAT COMMENT (SECOND TIME). NO SAFETY PLAN WAS
 SUBMITTED. PROVIDE PLAN SHOWING ALL THE PROPOSED
 EQUIPMENT (REMEMBER: PROPOSED USE IS NOT CLARIFIED).
 CLEARLY DEFINED ALL ROOM AREAS. PROVIDE COMPLETE
 EQUIPMENT, TABLES, FURNITURE REQUIRED FOR THE PROPOSED
 USE (SEC. 1001.4 FBC). PROVIDE OCCUPANT LOAD (SEC. 1004
 FBC), SHOW EGRESS PATH AND TRAVEL DISTANCES, DOORS
 SIZES, EXIT SIGNS, FIRE EXTINGUISHERS (SEC. 906 FBC),
 ETC.
  
 ORIGINAL COMMENT:
 C. PROVIDE ADDITIONAL INFORMATION REGARDING THE USE OF
 THIS SPACE SEE ALSO FBC 304.1 FOOD PROCESSING
 FACILITIES ESTABLISHMENTS AND COMMERCIAL KITCHENS.
  
 FBC 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING
 OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA
 AND DOCUMENTS.
 SEE THIS SECTION FOR MINIMUM PLAN REVIEW CRITERIA.
  
 RESPONSE:
 REPEAT COMMENT (SECOND TIME). NOT ADDRESSED.
  
 NEW COMMENTS:
 11- FLOOR PLANS SHOW EXISTING WALL EXHAUST FANS ON THE
 NORTH AND SOUTH SIDE. OPENINGS ARE NOT ALLOWED. SEE
 SEC. 705.8 FBC. AND REVISE AS REQUIRED.
  
 12- EXTERIOR WALLS REQUIRE A FIRE RESISTANCE RATING OF
 2 HOURS AS REQUIRED BY SEC. 1012.6 FBC-EXISTING
 BUILDING AND TABLE 602 FBC. PROVIDE COMPLETE DETAILS
 AND SPECIFICATIONS SHOWING COMPLIANCE WITH THE 2 HOUR
 FIRE RESISTANCE RATING.
  
 13- SHEET S-2:
 A)CLARIFY WHY STRUCTURAL NOTE #1 SPECIFIES CATEGORY
 III, WHILE THE WIND LOADS AT THE BOTTOM OF NEXT COLUMN
 SPECIFIES CATEGORY II. CLARIFY AS REQUIRED. IS THIS THE
 RISK CATEGORY?. IF SO, THEN SEE TABLE 1604.5 FBC AND
 REVISE AS REQUIRED.
  
 B) WIND LOADS INFORMATION: CLARIFY WHY ITEM "G"
 COMPONENT & CLADDING HEIGHT IS DIFFERENT THAN ITEM "H"
 MRH?. SEE BUILDING FOR CORRECT MEAN ROOF HEIGHT AND
 REVISE AS REQUIRED, INCLUDING THE DESIGN PRESSURES.
 SEC. 1609 FBC.
  
 14- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 INTERIOR PARTITIONS. SPECIFY ALL FRAMING MEMBERS ,
 SPACING, CONNECTORS, ETC. SEC. 107.2.1 CITY AMENDMENTS.
  
 NOTE: ADDITIONAL COMMENTS MAY ARISE BASED ON THE
 INFORMATION SUBMITTED BY THE DESIGN PROFESSIONAL TO
 ADDRESS ALL THE COMMENTS.
  
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]