| Plan Review Notes For Permit 18020521 |
| Permit Number |
18020521 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-02-28 12:24:42 | 1ST REVIEW: FBC 2017 6TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. WHERE A SEDIMENT TRAP IS NOT INCORPORATED AS PART OF | | | THE APPLIANCE, A SEDIMENT TRAP SHALL BE INSTALLED | | | DOWNSTREAM OF THE APPLIANCE SHUTOFF VALVE AS CLOSE TO | | | THE INLET OF THE APPLIANCE AS PRACTICAL. THE SEDIMENT | | | TRAP SHALL BE EITHER A TEE FITTING HAVING A CAPPED | | | NIPPLE OF ANY LENGTH INSTALLED VERTICALLY IN THE | | | BOTTOMMOST OPENING OF THE TEE. PER FBC FG 408.4 | | | | | | 2. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE | | | FBC-2014 FUEL GAS CODE SEC. 304. | | | | | | 3. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, LENGTH, | | | SIZE AND TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL | | | GAS CODE SEC. 502 THRU 505. | | | | | | 4. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL | | | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA | | | 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|