| 2018-03-06 11:07:15 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. THE FBC SPECIFIED FOR DESIGN IS NOT THE CURRENT |
| | CODE. PROVIDE CORRECTION. FBC PREFACE (ALSO SEE CURRENT |
| | CODES ABOVE) |
| | 2. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE |
| | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| | IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2 |
| | 3. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY |
| | WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC RE |
| | E3706.2, E3902 |
| | 4. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED |
| | PER CODE. SHOW ON PLAN ALL EXISTING ALARMS. IF NONE ARE |
| | EXISTING OR NOT TO CODE, SHOW AS NEW INSTALLATIONS. FBC |
| | R314.3, FBC 107.2.1 |
| | 5. THE WALL SPACING REQUIREMENTS FOR KITCHEN COUNTER |
| | SPACE STATE THAT RECEPTACLE OUTLETS SHALL BE INSTALLED |
| | SO THAT NO POINT ALONG THE WALL LINE IS MORE THAN 24 |
| | INCHES MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET |
| | IN THAT SPACE. THE PLAN PROVIDED DOES NOT SHOW ANY OF |
| | THE REQUIRED OUTLETS. PROVIDE CORRECTION. NEC |
| | 210.52(C)(1); FBC RE E3901.4 |
| | 6. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC |
| | 210.8(D); FBC RE E3902.10 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |
| | |