| Plan Review Notes For Permit 18020488 |
| Permit Number |
18020488 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-03-06 11:21:04 | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED | | | NFPA 70 2011 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | PAGE E-1.1 SHOWS TWO TENNANTS. | | | | | | PAGE E-3.1 SHOWS JUST ONE METER AND ONE PANEL, MAINS TO | | | BE GROUPED PER 230.72 | | | | | | CAN NOT FEED ONE SPACE THROUGH ANOTHER. CIRCUITS IN | | | SECOND SPACE LOOK TO BE COMING FROM OTHER SPACE. |
|