Plan Review Notes
Plan Review Notes For Permit 18020488
Permit Number 18020488
Review Stop E
Sequence Number 2
Notes
Date Text
2018-03-06 11:21:04FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E-1.1 SHOWS TWO TENNANTS.
  
 PAGE E-3.1 SHOWS JUST ONE METER AND ONE PANEL, MAINS TO
 BE GROUPED PER 230.72
  
 CAN NOT FEED ONE SPACE THROUGH ANOTHER. CIRCUITS IN
 SECOND SPACE LOOK TO BE COMING FROM OTHER SPACE.