| 2018-03-15 11:54:37 | RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW CHECKLIST. |
| | CODE: FBC 6TH EDITION (2017). |
| | |
| | 1- PROVIDE COMPLETE PLANS SHOWING LOCATION OF THE |
| | POWDER BATH ON THE FIRST FLOOR AND COMPLETE PLANS |
| | SHOWING THE LOCATION OF THE SECOND FLOOR BATHROOM TO BE |
| | RENOVATED AND ADDITION OF ONE FULL BATHROOM AS |
| | SPECIFIED ON THE PERMIT APPLICATION. NOTE: CLEARLY |
| | IDENTIFY ALL ROOMS ADJACENT TO ALL BATHROOMS TO VERIFY |
| | COMPLIANCE WITH THE MINIMUM ROOM DIMENSIONS. PROVIDE |
| | DEMOLITION PLAN SHOWING EXISTING CONDITIONS AND PLAN |
| | SHOWING PROPOSED CONDITIONS. SEC. 107.201 CITY |
| | AMENDMENTS. |
| | |
| | |
| | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN |
| | UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS |
| | SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING |
| | OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT |
| | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| | BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND |
| | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC, |
| | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE |
| | OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS |
| | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS |
| | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE |
| | OF THE PERSON RESPONSIBLE FOR THE DESIGN. |
| | |
| | 2- IT LOOKS LIKE THE LAVATORY ON THE EXISTING SECOND |
| | FLOOR BATHROOM MAY NOT COMPLY WITH THE MINIMUM 21" |
| | CLEARANCE DIMENSION REQUIRED BY SEC. R307.1 |
| | FBC-RESIDENTIAL. REVISE AS REQUIRED AND SHOW DIMENSION |
| | ON PLAN. |
| | |
| | R307.1 SPACE REQUIRED. |
| | FIXTURES SHALL BE SPACED IN ACCORDANCE WITH FIGURE |
| | R307.1, AND IN ACCORDANCE WITH THE REQUIREMENTS OF |
| | SECTION P2705.1. |
| | |
| | 3- VALUATION DECLARED IN THE PERMIT APPLICATION LOOKS |
| | TOO LOW BASED ON ALL THE SCOPE OF WORK. REVISE AS |
| | REQUIRED. |
| | |
| | FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING |
| | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE |
| | TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST |
| | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS |
| | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| | |
| | |
| | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO HELP EXPEDITE THE REVIEW PROCESS. |
| | |
| | ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| | DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY |
| | REVIEWED DRAWINGS. DON'T STAPLE OLD DRAWINGS TO PLANS. |
| | |
| | |