| Plan Review Notes For Permit 18020443 |
| Permit Number |
18020443 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-02-15 12:24:44 | PERMIT # 18020443 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | FAILED COMMENTS: | | | | | | 1) PROVIDE HYDRAULIC CALCULATIONS SUPPORTING THE USE OF | | | THE FLEXIBLE SPRINKLER DROPS AND THE ADDITIONAL | | | FRICTION LOSS ASSOCIATED WITH THESE PRODUCTS. | | | | | | 2) PROVIDE A FLEXIBLE DROP DETAIL INDICATING THE | | | MAXIMUM NUMBER OF BENDS PERMITTED AND THE MINIMUM BEND | | | RADIUS PERMITTED IN THE LISTING DATA. | | | | | | 3) SUBMIT PRODUCT DATA FOR THE FLEXIBLE SPRINKLER DROPS | | | PROPOSED TO BE INSTALLED. INDICATE IF THE DROPS ARE | | | BRAIDED OR UNBRAIDED. | | | | | | 4) INDICATE THE MAXIMUM LENGTH OF FLEXIBLE DROP TO BE | | | USED. | | | | | | SUE ELLEN CALDERON | | | ASSISTANT FIRE MARSHAL | | | [email protected] | | | |
|