| 2018-02-13 18:44:00 | RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS. |
| | CODE: FBC 6TH EDITION (2017). |
| | |
| | 1- INSTALLATION SCHEDULE SUBMITTED: |
| | A) CALCULATED DESIGN PRESSURES ARE INCORRECT. ALSO, THE |
| | DESIGN CRITERIA TAKEN INTO CONSIDERATION DOESN'T MATCH |
| | ACTUAL BUILDING. THERE IS INFORMATION IN THE DESIGN |
| | CRITERIA THAT DOESN'T SEEM TO APPLY FOR THIS PROJECT. |
| | PROVIDE COMPLETE SIGNED AND SEALED WIND LOAD |
| | CALCULATIONS THAT CORRESPOND TO THE ACTUAL BUILDING OR |
| | USE THE TABLE R301.2(2) OF THE FBC-RESIDENTIAL, 6TH |
| | EDITION (2017) TO OBTAIN THE CORRESPONDING DESIGN |
| | PRESSURES. NOTE: IF USING THE FBC TABLE TAKE INTO |
| | CONSIDERATION THAT DESIGN PRESSURES NEED TO BE ADJUSTED |
| | TO BUILDING EXPOSURE "C" AND THE ACTUAL BUILDING MEAN |
| | ROOF HEIGHT. SEE TABLE R301.2(3) FBC-RESIDENTIAL. |
| | |
| | B) REVISE ANCHOR SPACING BASED ON THE REVISED DESIGN |
| | PRESSURES. COORDINATE WITH ITEM #1(A) ABOVE. SEC. |
| | R301.1 FBC-RESIDENTIAL. |
| | |
| | C) INSTALLATION SCHEDULE IS MISSING THE GLASS |
| | SEPARATION DISTANCE. SEC. R301.1 FBC-RESIDENTIAL. |
| | |
| | D) SECTION OR TYPE "A" SPECIFIED ON THE TOP CONNECTION |
| | IS FOR POURED CONCRETE SUBSTRATE ONLY NOT FOR WOOD |
| | FRAME AS SHOWN ON SCHEDULE SUBMITTED. SEE DETAIL "A" ON |
| | SHEET 6 OF 20 AND REVISE AS REQUIRED. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | E) SECTION OR TYPE "U" SPECIFIED ON THE TOP CONNECTION |
| | IS FOR WOOD SUBSTRATE ONLY NOT FOR CONCRETE AS SHOWN ON |
| | SCHEDULE SUBMITTED. SEE DETAIL "U" ON SHEET 17 OF 20 |
| | AND REVISE AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | F) CLARIFY WHAT'S CONNECTION TYPE 3/8"WM AND CONNECTION |
| | TYPE ADJ SILL?. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | G) TOP CONNECTION USING SECTION OR TYPE "U" DETAIL |
| | NEEDS TO SPECIFY LAG SCREWS NOT TAPCONS. SEE DETAIL "U" |
| | AND REVISE AS REQUIRED. SEC. R301.1 FBC-RESIDENTIAL. |
| | |
| | H) PROVIDE COMPLETE SPECIFICATIONS FOR TYPE OF ANCHOR |
| | TO BE USED. SPECIFY ANCHOR DIAMETER AND LENGTH TO |
| | VERIFY COMPLIANCE WITH THE PRODUCT APPROVAL |
| | REQUIREMENTS FOR MINIMUM EMBEDMENT. SEC. R301.1 |
| | FBC-RESIDENTIAL. |
| | |
| | I) CLARIFY WHAT ARE THE "ALLOWABLE PRESSURES" SPECIFIED |
| | NEXT TO THE DESIGN PRESSURES STAND FOR AND, CLARIFY |
| | WHERE ARE THESE PRESSURES TAKEN FROM?. COORDINATE WITH |
| | ITEM #1(A) ABOVE. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |