| Date |
Text |
| 2018-05-07 10:13:38 | 1) THE SUBMITTTED SIZING TABLES FOR THE GAS SYSTEM ARE |
| | FROM THE 2014 FBC-FUEL GAS CODE. THE CODE IN EFFECT FOR |
| | THIS PERMIT IS THE 2017 FBC-FUEL GAS.SUBMIT TWO COPIES |
| | OF THE SIZING TABLES FROM THE 2017 FBC-FUEL GAS CODE. |
| | 4TH REQUEST. |
| | 2) THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE |
| | ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE |
| | THE EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, |
| | THE EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE |
| | OPERATING SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM |
| | THAT SHOWS THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD |
| | OF EACH APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO |
| | EACH APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH |
| | OF PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE |
| | OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE |
| | EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE |
| | SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE |
| | REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES. |
| | FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR |
| | SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3. |
| | 3) SHOW THE DISTANCE FROM THE MEDIUM PRESSURE REGULATOR |
| | FOR THE EXISTING APPLIANCES TO THE MOST REMOTE OUTLET |
| | ON THE SYSTEM. |
| | 4) A GAS SIZING TABLE FOR SCH. 40 METALLIC PIPE 2 PSI |
| | SHOWING A 70 FEET LENGTH HAS BEEN SUBMITTED AND ALSO A |
| | SIZING TABLE FOR PE PIPE AT A 2 PSI SYSTEM AT 90 FEET |
| | LENGTH. WHICH IS IT? METALLIC PIPE IS NOT PERMITTED TO |
| | BE UNDERGROUND PER 2017 FBC - FUEL GAS SEC. 404.11.1. |
| | THE PE PIPE IS UNDERSIZED IF THE LENGTH IS 90 FEET. THE |
| | MAXIMUM BTU LOAD IS 1,130,000. CLARIFY. |
| | 5) SIZE THE PIPE FROM THE GAS METER TO THE FIRST TEE |
| | AND ALSO FROM THE TEE FITTING TO THE MEDIUM PRESSURE |
| | REGULATOR FOR THE EXISTING APPLIANCES. |
| | |
| | NOTE: SOMEONE FROM THE CONTRACTOR NEEDS TO COME TO THE |
| | BUILDING DIVISION AND STRAIGHTEN OUT ALL THE PAPERWORK |
| | INTO TWO COMPLETE PACKAGES FOR PLAN REVIEW. AS OF NOW, |
| | THIS PAPERWORK IS A CONFUSING MESS. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |