| 2018-03-28 14:46:48 | 03/28/2018 3RD GAS REVIEW**DENIED** PLEASE CALL AND |
| | SPEAK TO TIM LARGE 561-805-6692 TO SET A MEETING DATE |
| | AND TIME TO REVIEW THE PLAN DEFICIENCIES AS THIS IS THE |
| | 3RD REVIEW AND ONLY 3 OF 10 COMMENTS HAVE BEEN |
| | RESOLVED.DO NOT RESUBMIT WITHOUT FIRST HAVING A |
| | MEETING. IT IS ADVISED YOU ALSO CONTACT THE ELECTRIC |
| | PLAN REVIEW AND MEET AT THE SAME TIME. |
| | |
| | 1) WE ARE CURRENTLY USING THE 2017 FBC CODE 6TH ED. |
| | YOUR PAPERWORK STILL REFERS TO THE 2014 FOR THE 3RD |
| | TIME |
| | |
| | 2) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE |
| | LENGTH OF ALL CUT SECTIONS OF PIPE. YOU ARE NOT SHOWING |
| | THE PIPING SIZE LEAVING THE GAS METER. 2017 FBC-FUEL |
| | GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC-RES SEC. |
| | G2413.4.1, G2413.4.2. |
| | |
| | 3) SUBMIT FULL INSTALLATION MANUAL FOR THE GAS PRESSURE |
| | REGUALTOR. FGC 410.1 |
| | |
| | 4) SUBMIT 2 COPIES OF SIZING TABLES FOR ALL PIPING |
| | MATERIAL BEING USED. YOU SUPPLIED SCH 40 METALLIC |
| | SIZING CHART BUT YOUR ISOMETRIC SHOWS YOUR RUNNING NE |
| | P.E. SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES |
| | USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE |
| | PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM |
| | THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE |
| | DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL |
| | GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1) |
| | THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8, |
| | G2413.1, G2413.2, & G2413.3. |
| | |
| | 5) REVISE YOUR ISOMETRIC TO SHOW REQUIRED SEDIMENT TRAP |
| | ON THE GENERATOR. FGC 408.3 |
| | |
| | 6) YOUR PLAN STILL IS SHOWING BOTH 38KW AND 48KW. |
| | PLEASE REMOVE THE INCORRECT SHEETS. FBC 107.2.1 |
| | |
| | TIM HUNT |
| | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER |
| | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | 561-805-6695 |
| | [email protected] |
| | |