Plan Review Notes
Plan Review Notes For Permit 18020397
Permit Number 18020397
Review Stop G
Sequence Number 1
Notes
Date Text
2018-02-16 12:35:3002/16/2018 1ST GAS REVIEW**DENIED**
  
 PLEASE BE ADVISED THE CURRENT CODE IN EFFECT IN THE 6TH
 ED. 2017 FBC. SOME OF YOUR SIZING CHARTS REFERENCE THE
 2014 FBC
  
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1) WHAT SIZE GENERATOR IS BEING USED? PLAN SHOWS BOTH
 38KW AND 48KW. FBC 107.2.1
  
 2) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES SEC. G2413
  
 3) WHAT IS THE EXISTING SYSTEM PRESSURE? IS IT YOUR
 INTENT TO CHANGE THE 12" WC TO 2LB SYSTEM OR IS THE
 SYSTEM ALREADY 2 PSI. FBC 107.2.1
  
 4) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS
 SECS.401.8 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4
 (37) OR 2014 FBC-RES. SEC. G2413. THE PLANS INDICATE AN
 EXISTING GAS METER. THE BTU LOAD OF THE EXISTING GAS
 SYSTEM MUST BE ADDED INTO THE TOTAL BTU LOAD ON THE
 SYSTEM TO ENSURE THE EXISTING SYSTEM IS PROPERLY SIZED.
 IF UNDERSIZED, THE EXISTING SYSTEM MUST BE REDONE TO
 ENSURE A SAFE OPERATING SYSTEM. SUBMIT A GAS PIPING
 RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING
 APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE
 SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE
 DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT
 OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF
 THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN
 A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO
 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE
 EXISTING APPLIANCES. FGC SECS. 401.4, 401.8, 402.1,
 402.2, 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1,
 G2413.2, G2413.3
  
 5) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2017 FGC SEC.410.1.
  
 6) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. FBC-FUEL GAS SEC.409.4,
 FBC-RESIDENTIAL SEC. G 2420.4. I
  
 7) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL
 GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES 402.4
 (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. G2412.4,
 G2412.8, G2413.1, G2413.2, & G2413.3.
  
 8) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE
 APPLIANCE. COMPLY WITH 2017 FBC-FUEL GAS TABLE 402.4
 (28) FOR THE PROPER PIPE SIZE AND BTU LOAD
  
 9) REVISE YOUR FLAT DRAWING TO SHOW THE REQUIRED
 SEDIMENT TRAP. 2017 FBC-FUEL GAS 408.4.
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  
  