| 2018-02-15 05:34:29 | 02/15/2018 1ST GAS REVIEW**DENIED ** | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1) TOTAL JOB COST SEEMS LOW. VALUE MUST INCLUDE COST OF | | | ALL EQUIPMENT INCLUDING TANKLESS AND STOVE. PROVIDE | | | BONA FIDE SIGNED CONTRACT PER WPB AMENDMENTS TO THE FBC | | | 109.3 | | | | | | 2) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / | | | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY | | | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND | | | FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014 | | | FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED | | | AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS | | | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF | | | INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1 | | | | | | 3) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED GAS | | | APPLIANCES. WHERE COMBUSTION AIR IS PROVIDED BY THE | | | BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM | | | SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN | | | ADDITION TO THE REQUIRED VENTILATION AIR. FGC | | | SEC.304.9.3 OR FBCR G2407.9.3. | | | | | | | | | TIM HUNT | | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | 561-805-6695 | | | [email protected] | | | |
|