Plan Review Notes
Plan Review Notes For Permit 18020385
Permit Number 18020385
Review Stop P
Sequence Number 2
Notes
Date Text
2018-08-20 11:34:092ND REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. SHEET P1.1: THE CONDENSATE FROM AHU-7 & 8 SHALL NOT
 DRAIN INTO THE CITY SANITARY PER SECTION 90-126 CITY OF
 WPB CODE OF ORDINANCES. PLEASE PROVIDE AN APPROVED
 LOCATION SUCH AS A STORM DRAIN OR PERMEABLE GROUND.
  
 2. SHT. P1.1 - P2 THE SINK IN THE PHARMACY S1 SHALL
 CONNECT TO THE BUILDING DRAIN DOWN STREAM OF THE
 BATHROOM GROUP. PER FBC PL 912.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  