| Date |
Text |
| 2018-07-31 12:52:31 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18020385 |
| | 7/31/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE SUBMITTED AC CALCULATIONS FROM THE EOR INDICATE |
| | THAT THE HP SYSTEMS 1-5, AS SHOWN IN THE SCHEDULES ON |
| | SHEET M3, ARE OVERSIZED IN COOLING AND HEATING |
| | CAPACITIES- SEE SECTION C403.2.2 FBC EC. MISSING FROM |
| | THE CALCULATIONS ARE THE MINI-SPLIT SYSTEMS 6, 7, & 8. |
| | |
| | 2) THE SUBMITTED COMCHECK ENERGY COMPLIANCE CERTIFICATE |
| | SHOWS CAPACITIES FOR COOLING AND HEATING THAT DON'T |
| | MATCH THE CAPACITIES IN THE SCHEDULES. PLEASE NOTE THAT |
| | THE EFFICIENCY RATING OF 12.30 EER FOR SYSTEM #3 DOES |
| | NOT MATCH THE SCHEDULE WHICH INDICATES 11.9 EER. |
| | |
| | 3) M1.1: VERIFY MIMIMUM 10' CLEARANCE EXISTS FROM THE |
| | NEW O/A INTAKE LOUVER TO THE STREET- SECTION 401.4 FBC |
| | M. |
| | |
| | 4) SHEET P1.1: THE CONDENSATE FROM AHU-7 & 8 SHALL NOT |
| | DRAIN INTO THE CITY SANITARY PER SECTION 90-126 CITY OF |
| | WPB CODE OF ORDINANCES. PLEASE PROVIDE AN APPROVED |
| | LOCATION SUCH AS A STORM DRAIN OR PERMEABLE GROUND. |
| | |
| | 5) REQUIRED SUBMITTALS: NOA'S OR PRODUCT APROVALS FOR |
| | THE LOUVERS AND AC STANDS, ERV, DUCT SMOKE DETECTORS, |
| | C02 SENSORS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |