| Date |
Text |
| 2018-08-20 17:58:34 | CHANGE OF OCCUPANCY ((M) , SECOND BUILDING REVIEW |
| | COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS |
| | |
| | |
| | ORIGINAL COMMENT: |
| | 1) CODE INFORMATION SHEET A0.1: |
| | CODE ANALYSIS AND PROJECT DATE INDICATES THIS IS A |
| | LEVEL III ALTERATION. PLEASE NOTE THIS IS A CHANGE OF |
| | OCCUPANCY SEE THE 2017 FBC-EXISTING BUILDING CODE |
| | CHAPTER 10. |
| | EXIST. BLDG. CODE 1001.2.2.1 PARTIAL CHANGE OF |
| | OCCUPANCY. WHERE THE OCCUPANCY CLASSIFICATION OR GROUP |
| | OF A PORTION OF AN EXISTING BUILDING IS CHANGED, |
| | SECTION 1012 SHALL APPLY. |
| | |
| | RESPONSE: |
| | THE CORRECT CLASSIFICATION OF WORK IS ALTERATION LEVEL |
| | 3 AND CHANGE OF OCCUPANCY. SEC. 501.1 FBC-EXISTING |
| | BUILDING. IT IS IMPORTANT TO CLEARLY SPECIFY SCOPE OF |
| | WORK. TYPICALLY, ALTERATION LEVEL 3 PROJECTS REQUIRE A |
| | CERTIFICATE OF COMPLETION, BUT WHEN THE SCOPE OF WORK |
| | INVOLVES A CHANGE OF OCCUPANCY, THEN A CERTIFICATE OF |
| | OCCUPANCY IS REQUIRED. |
| | SINCE THIS IS A CHANGE OF OCCUPANCY A CERTIFICATE OF |
| | OCCUPANCY SHALL BE USED AS REQUIRED BY SEC. 1001.3 |
| | FBC-EXISTING BUILDING. |
| | |
| | ORIGINAL COMMENT: |
| | 2) SHEET S3 THE TABLE FOR PRESSURES DOES NOT STATE IT |
| | IS FOR 10 SQ. FT., THE TABLE DOES STATE THE PRESSURES |
| | ARE IN VASD. THE WALL PRESSURES FOR WALL ZONE 4 ARE 4 |
| | PSF LOW, WE FIGURE- 49.24 PSF AND WALL ZONE 5 THE |
| | PRESSURES OF -60.76 TAKEN FOR A MEAN ROOF HEIGHT OF 35 |
| | FEET. THIS BUILDING IS A MEAN ROOF HEIGHT GIVEN AT 34 |
| | FEET MEAN ROOF HEIGHT. |
| | |
| | RESPONSE: |
| | THE 10% REDUCTION OF GCP VALUES IS OK (FIGURE 30.4-1 |
| | ASCE 7-10) BUT THE HEIGHT SPECIFIED ON SHEET S3 SEEMS |
| | TO BE INCORRECT. IT DOESN'T MATCH HEIGHT SHOWN ON |
| | SHEETS A7 AND A8. REVISE AS REQUIRED. ALSO, THE DESIGN |
| | PRESSURES STILL DON'T CLARIFY THE EFFECTIVE WIND AREA. |
| | ARE THE VALUES GIVEN FOR 10PSF?. PLEASE CLARIFY. |
| | ACCORDING TO NOTE #4 OF FIGURE 30.4-1 EACH COMPONENT |
| | SHALL BE DESIGNED FOR MAXIMUM POSITIVE AND NEGATIVE |
| | PRESSURES. THIS IS REQUIRED FOR PROPER REVIEW OF |
| | PRODUCT APPROVALS SUBMITTED. |
| | |
| | 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A RESPONSE LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | NEW COMMENTS: |
| | 4) FLOOR PLAN LAYOUT WAS CHANGED. PRELIMINARY |
| | MERCHANDISE PLAN SHEET F-1P WAS NOT REVISED REFLECTING |
| | THE PROPOSED CHANGES. PROVIDE REVISED SHEET. SEC. |
| | 107.2.1 CITY AMENDMENTS. |
| | |
| | 5)FIRE SPRINKLER SHEET FP-2 WAS REVISED. NEED THE |
| | ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY |
| | SEC. 61G15-23.003 F.A.C. DIGITAL SIGNATURE IS ONLY FOR |
| | DIGITAL SUBMITTALS. THIS IS NOT A DIGITAL SUBMITTAL. |
| | |
| | 6- INFORMATION ONLY: FLOOR PLAN NOTE #4 ON SHEET A1 |
| | CALL FOR AWNING REPLACEMENT. COMPLETE DRAWINGS AND |
| | SPECIFICATIONS NEED TO BE SUBMITTED UNDER A SEPARATE |
| | PERMIT. |
| | |
| | ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| | DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY |
| | REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |