Plan Review Notes
Plan Review Notes For Permit 18020385
Permit Number 18020385
Review Stop B
Sequence Number 2
Notes
Date Text
2018-08-20 17:58:34CHANGE OF OCCUPANCY ((M) , SECOND BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS
  
  
 ORIGINAL COMMENT:
 1) CODE INFORMATION SHEET A0.1:
 CODE ANALYSIS AND PROJECT DATE INDICATES THIS IS A
 LEVEL III ALTERATION. PLEASE NOTE THIS IS A CHANGE OF
 OCCUPANCY SEE THE 2017 FBC-EXISTING BUILDING CODE
 CHAPTER 10.
 EXIST. BLDG. CODE 1001.2.2.1 PARTIAL CHANGE OF
 OCCUPANCY. WHERE THE OCCUPANCY CLASSIFICATION OR GROUP
 OF A PORTION OF AN EXISTING BUILDING IS CHANGED,
 SECTION 1012 SHALL APPLY.
  
 RESPONSE:
 THE CORRECT CLASSIFICATION OF WORK IS ALTERATION LEVEL
 3 AND CHANGE OF OCCUPANCY. SEC. 501.1 FBC-EXISTING
 BUILDING. IT IS IMPORTANT TO CLEARLY SPECIFY SCOPE OF
 WORK. TYPICALLY, ALTERATION LEVEL 3 PROJECTS REQUIRE A
 CERTIFICATE OF COMPLETION, BUT WHEN THE SCOPE OF WORK
 INVOLVES A CHANGE OF OCCUPANCY, THEN A CERTIFICATE OF
 OCCUPANCY IS REQUIRED.
 SINCE THIS IS A CHANGE OF OCCUPANCY A CERTIFICATE OF
 OCCUPANCY SHALL BE USED AS REQUIRED BY SEC. 1001.3
 FBC-EXISTING BUILDING.
  
 ORIGINAL COMMENT:
 2) SHEET S3 THE TABLE FOR PRESSURES DOES NOT STATE IT
 IS FOR 10 SQ. FT., THE TABLE DOES STATE THE PRESSURES
 ARE IN VASD. THE WALL PRESSURES FOR WALL ZONE 4 ARE 4
 PSF LOW, WE FIGURE- 49.24 PSF AND WALL ZONE 5 THE
 PRESSURES OF -60.76 TAKEN FOR A MEAN ROOF HEIGHT OF 35
 FEET. THIS BUILDING IS A MEAN ROOF HEIGHT GIVEN AT 34
 FEET MEAN ROOF HEIGHT.
  
 RESPONSE:
 THE 10% REDUCTION OF GCP VALUES IS OK (FIGURE 30.4-1
 ASCE 7-10) BUT THE HEIGHT SPECIFIED ON SHEET S3 SEEMS
 TO BE INCORRECT. IT DOESN'T MATCH HEIGHT SHOWN ON
 SHEETS A7 AND A8. REVISE AS REQUIRED. ALSO, THE DESIGN
 PRESSURES STILL DON'T CLARIFY THE EFFECTIVE WIND AREA.
 ARE THE VALUES GIVEN FOR 10PSF?. PLEASE CLARIFY.
 ACCORDING TO NOTE #4 OF FIGURE 30.4-1 EACH COMPONENT
 SHALL BE DESIGNED FOR MAXIMUM POSITIVE AND NEGATIVE
 PRESSURES. THIS IS REQUIRED FOR PROPER REVIEW OF
 PRODUCT APPROVALS SUBMITTED.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A RESPONSE LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 NEW COMMENTS:
 4) FLOOR PLAN LAYOUT WAS CHANGED. PRELIMINARY
 MERCHANDISE PLAN SHEET F-1P WAS NOT REVISED REFLECTING
 THE PROPOSED CHANGES. PROVIDE REVISED SHEET. SEC.
 107.2.1 CITY AMENDMENTS.
  
 5)FIRE SPRINKLER SHEET FP-2 WAS REVISED. NEED THE
 ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY
 SEC. 61G15-23.003 F.A.C. DIGITAL SIGNATURE IS ONLY FOR
 DIGITAL SUBMITTALS. THIS IS NOT A DIGITAL SUBMITTAL.
  
 6- INFORMATION ONLY: FLOOR PLAN NOTE #4 ON SHEET A1
 CALL FOR AWNING REPLACEMENT. COMPLETE DRAWINGS AND
 SPECIFICATIONS NEED TO BE SUBMITTED UNDER A SEPARATE
 PERMIT.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved