Plan Review Notes
Plan Review Notes For Permit 18020385
Permit Number 18020385
Review Stop P
Sequence Number 1
Notes
Date Text
2018-03-20 09:43:241ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.5.1 SIDE
 WALL. THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG
 MINIMUM, LOCATED 12 INCHES MAXIMUM FROM THE REAR WALL
 AND EXTENDING 54 INCHES MINIMUM FROM THE REAR WALL.
  
 2. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.7
 DISPENSERS. TOILET PAPER DISPENSERS SHALL COMPLY WITH
 309.4 AND SHALL BE 7 INCHES MINIMUM AND 9 INCHES
 MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO THE
 CENTERLINE OF THE DISPENSER.
  
 3.PLEASE SHOW THE CLEAR FOOR SPACE WITH DIMENSIONS ,
 FOR THE TOILET AND LAVATORY. PER FBC ACC 604.3.1, 606.2
  
 4. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.2
 LOCATION.THE WATER CLOSET SHALL BE POSITIONED WITH A
 WALL OR PARTITION TO THE REAR AND TO ONE SIDE. THE
 CENTERLINE OF THE WATER CLOSET SHALL BE 16 INCHES
 MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE WALL OR
 PARTITION. IT APPEARS THAT THE DIMENSION MAY HAVE BEEN
 SHOWN BUT IT DID NOT LINE UP WITH THE TOILET.
  
 5. SHT P4 DETAIL #7 THE WALL DRAIN BOX WHEN CONNECTED
 TO THE STORM DRAINAGE SHALL HAVE A BACKWATER VALVE. PER
 FBC PL 1101.9
  
 6. SHT P4 DETAIL # 2 THE REQUIRED TEMPERED WATER AT THE
 LAVATORY IN THE BATHROOM SHALL BE DELIVERED THROUGH A
 WATER TEMPERATURE LIMITING DEVISE THAT MEETS ASSE 1070
 OR CSA B125.3 THE TEMPERING VALVE SPARCO 102C LISTED ON
 DETAIL #2 DOES NOT COMPLY. THE REQUIREMENT FOR TEMPERED
 WATER ONLY ONLY APPLIES TO THE LAVATORY'S IN THE
 BATHROOMS . PER FBC PL 416.5
  
 7. PLEASE SHOW THAT THE 19 GAL WATER HEATER IS LARGE
 ENOUGH TO SUPPLY THE 5 SINKS WITH HOT OR TEMPERED WATER
 YOU CAN REFERENCE APPENDIX E OF THE FBC PL OR
 MANUFACTURE SIZING. PER WPB AMEND FBC AMEND TO FBC
 107.2.1
  
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  