| 2018-03-20 09:43:24 | 1ST REVIEW: FBC 2017 6TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.5.1 SIDE |
| | WALL. THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG |
| | MINIMUM, LOCATED 12 INCHES MAXIMUM FROM THE REAR WALL |
| | AND EXTENDING 54 INCHES MINIMUM FROM THE REAR WALL. |
| | |
| | 2. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.7 |
| | DISPENSERS. TOILET PAPER DISPENSERS SHALL COMPLY WITH |
| | 309.4 AND SHALL BE 7 INCHES MINIMUM AND 9 INCHES |
| | MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO THE |
| | CENTERLINE OF THE DISPENSER. |
| | |
| | 3.PLEASE SHOW THE CLEAR FOOR SPACE WITH DIMENSIONS , |
| | FOR THE TOILET AND LAVATORY. PER FBC ACC 604.3.1, 606.2 |
| | |
| | 4. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.2 |
| | LOCATION.THE WATER CLOSET SHALL BE POSITIONED WITH A |
| | WALL OR PARTITION TO THE REAR AND TO ONE SIDE. THE |
| | CENTERLINE OF THE WATER CLOSET SHALL BE 16 INCHES |
| | MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE WALL OR |
| | PARTITION. IT APPEARS THAT THE DIMENSION MAY HAVE BEEN |
| | SHOWN BUT IT DID NOT LINE UP WITH THE TOILET. |
| | |
| | 5. SHT P4 DETAIL #7 THE WALL DRAIN BOX WHEN CONNECTED |
| | TO THE STORM DRAINAGE SHALL HAVE A BACKWATER VALVE. PER |
| | FBC PL 1101.9 |
| | |
| | 6. SHT P4 DETAIL # 2 THE REQUIRED TEMPERED WATER AT THE |
| | LAVATORY IN THE BATHROOM SHALL BE DELIVERED THROUGH A |
| | WATER TEMPERATURE LIMITING DEVISE THAT MEETS ASSE 1070 |
| | OR CSA B125.3 THE TEMPERING VALVE SPARCO 102C LISTED ON |
| | DETAIL #2 DOES NOT COMPLY. THE REQUIREMENT FOR TEMPERED |
| | WATER ONLY ONLY APPLIES TO THE LAVATORY'S IN THE |
| | BATHROOMS . PER FBC PL 416.5 |
| | |
| | 7. PLEASE SHOW THAT THE 19 GAL WATER HEATER IS LARGE |
| | ENOUGH TO SUPPLY THE 5 SINKS WITH HOT OR TEMPERED WATER |
| | YOU CAN REFERENCE APPENDIX E OF THE FBC PL OR |
| | MANUFACTURE SIZING. PER WPB AMEND FBC AMEND TO FBC |
| | 107.2.1 |
| | |
| | |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |