| 2018-03-12 16:39:30 | 1ST REVIEW FBC-2017 MECHANICAL, ENERGY CONSERVATION |
| | CODES |
| | PERMIT #18020385 |
| | 3/12/18 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW |
| | AC SYSTEMS- SECTION C403.2.1 FBC-17 ENERGY |
| | CONSERVATION. |
| | |
| | 2) SHEET M3: THE MINIMUM O/A SCHEDULE SHOWS THE NUMBER |
| | OF OCCUPANTS IN THE RETAIL AREAS TO BE NOT IN |
| | COMPLIANCE WITH TABLE 403.1.1. BASED ON THE TABLE THE |
| | NUMBER OF OCCUPANTS SHALL BE: (AHU-1 53 PERSONS) AHU-2 |
| | (31 PERSONS), AND AHU-3 (47 PERSONS). PLEASE REVISE THE |
| | CALCULATIONS AND PLANS ACCORDINGLY. |
| | |
| | 3) M1: DUCT SMOKE DETECTORS ARE REQUIRED IN THE SUPPLY |
| | SYSTEMS OF AHU'S 1, 2, & 3- SECTION 606.2.1. |
| | |
| | 4) M1 & A4: PLEASE SHOW THE LOCATIONS OF THE DIFFUSERS |
| | AND RETURN GRILLS IN THE REFLECTIVE CEILING PLAN. |
| | |
| | 5) M2: PROVIDE A GUARD ALONG THE ROOF EDGE IN THE AREA |
| | OF HP 1 & 2 OR PLACE A NOTE TO INDICATE THE EXISTING |
| | PARAPET IS A MINIMUM 42" HIGH ABOVE THE FINISHED ROOF |
| | SURFACE- SEE SECTION 304.11 |
| | |
| | 6) M2: PROVIDE WIND LOAD ENGINEERING FOR INSTALLTION OF |
| | THE NEW ROOFTOP STANDS AND CONDENSING UNITS- SECTION |
| | 301.15. PLEASE INCLUDE THE WIND DESIGN CRITERIA IN |
| | ACCORDANCE WITH SECTION1609 FBC-17 BUILDING, AND SUBMIT |
| | THE MIAMI-DADE NOA FOR THE CONDENSER STANDS WITH |
| | MARKUPS AND APPROVAL STAMP BY THE EOR. |
| | |
| | 7) M3: THE EQUIPMENT SCHEDULE FOR THE MINI-SPLIT SYSTEM |
| | IS INCOMPLETE. PLEASE PROVIDE THE COOLING AND HEATING |
| | CAPACITIES OF THE SYSTEM. |
| | |
| | 8) PROVIDE A FLORIDA PRODUCT APPROVAL AND/OR A |
| | MIAMI-DADE NOA FOR THE O/A LOUVER, AND A SUBMITTAL FOR |
| | THE O/A AIR MOTORIZED DAMPERS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |