Plan Review Notes
Plan Review Notes For Permit 18020376
Permit Number 18020376
Review Stop B
Sequence Number 1
Notes
Date Text
2018-02-13 08:40:36PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) ASTM C926 AND FBC-R 702.1 REQUIRES THREE COATS OF
 STUCCO WITH A TOTAL THICKNESS OF 7/8" WHEN INSTALLED
 OVER WIRE LATH.
  
 2) CLARIFY THE SCOPE OF THE REVISION. THE PLANS THAT
 WERE SUBMITTED INDICATE THAT THE SECOND FLOOR OF THE
 REAR BUILDING WHICH CURRENTLY HAS WOOD SIDING IS TO BE
 STUCCOED. THE SCOPE OF WORK ON THE REVISION IS TO
 RE-STUCCO THE EXTERIOR WALLS OF SECOND FLOOR APARTMENT
 AND BACK HOUSE. FBC 107.2.1