| Plan Review Notes For Permit 18020376 |
| Permit Number |
18020376 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-02-13 08:40:36 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) ASTM C926 AND FBC-R 702.1 REQUIRES THREE COATS OF | | | STUCCO WITH A TOTAL THICKNESS OF 7/8" WHEN INSTALLED | | | OVER WIRE LATH. | | | | | | 2) CLARIFY THE SCOPE OF THE REVISION. THE PLANS THAT | | | WERE SUBMITTED INDICATE THAT THE SECOND FLOOR OF THE | | | REAR BUILDING WHICH CURRENTLY HAS WOOD SIDING IS TO BE | | | STUCCOED. THE SCOPE OF WORK ON THE REVISION IS TO | | | RE-STUCCO THE EXTERIOR WALLS OF SECOND FLOOR APARTMENT | | | AND BACK HOUSE. FBC 107.2.1 |
|