| Plan Review Notes For Permit 18020367 |
| Permit Number |
18020367 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-02-13 15:55:41 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT #18020367 | | | 2/13/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) CLARIFY HOW THE NEW SYSTEM WAS SIZED- PROVIDE HEAT | | | LOAD CALCULATIONS- SECTION 312.1 | | | | | | 2) CONTINUOUS VENTILATION IS REQUIRED IN THE POWER | | | (BATTERY STORAGE) ROOM AT A RATE THAT WILL LIMIT THE | | | MAXIMUM CONCENTRATION OF HYDROGEN TO 1.0 % OF THE TOTAL | | | VOLUME OF THE ROOM- SECTION 502.4.1 THE MINIMUM RATE | | | SHALL BE NOT LESS THAN 1.0 CFM PER SQ. FT. - SECTION | | | 502.4.2. | | | | | | 3) PROVIDE THE WIND LOAD DESIGN CRITERIA AND ENGINEERED | | | DETAILS FOR INSTALLATION OF THE EXTERIOR CONDENSER- | | | SECTION 1609 FBC-17 BUILDING. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|