Plan Review Notes
Plan Review Notes For Permit 18020367
Permit Number 18020367
Review Stop M
Sequence Number 1
Notes
Date Text
2018-02-13 15:55:411ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18020367
 2/13/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) CLARIFY HOW THE NEW SYSTEM WAS SIZED- PROVIDE HEAT
 LOAD CALCULATIONS- SECTION 312.1
  
 2) CONTINUOUS VENTILATION IS REQUIRED IN THE POWER
 (BATTERY STORAGE) ROOM AT A RATE THAT WILL LIMIT THE
 MAXIMUM CONCENTRATION OF HYDROGEN TO 1.0 % OF THE TOTAL
 VOLUME OF THE ROOM- SECTION 502.4.1 THE MINIMUM RATE
 SHALL BE NOT LESS THAN 1.0 CFM PER SQ. FT. - SECTION
 502.4.2.
  
 3) PROVIDE THE WIND LOAD DESIGN CRITERIA AND ENGINEERED
 DETAILS FOR INSTALLATION OF THE EXTERIOR CONDENSER-
 SECTION 1609 FBC-17 BUILDING.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  