| Notes |
| Date |
Text |
| 2018-03-07 14:01:46 | 1ST REVIEW: FBC 2017 6TH ED. RESIDENTIAL | | | 1ST REVIEW FBC 2017 EXISTING BUILDING | | | | | | | | | PROVIDE ELECTRICAL AS FOLLOWS: | | | E3901.2.1 SPACING. RECEPTACLES SHALL BE INSTALLED SO | | | THAT NO POINT MEASURED HORIZONTALLY ALONG THE FLOOR | | | LINE OF ANY WALL SPACE IS MORE THAN 6 FEET (1829 MM), | | | FROM A RECEPTACLE OUTLET. | | | FBCRE3902.12 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION. | | | FBCRE3903.3 ADDITIONAL LOCATIONS. AT LEAST ONE | | | WALL-SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE | | | INSTALLED TO PROVIDE ILLUMINATION ON THE EXTERIOR SIDE | | | OF EACH OUTDOOR EGRESS DOOR HAVING GRADE LEVEL ACCESS | | | FBCRE4002.14 TAMPER-RESISTANT RECEPTACLES IN AREAS | | | SPECIFIED IN SECTION E3901.1, 125-VOLT, 15- AND | | | 20-AMPERE RECEPTACLES SHALL BE LISTED TAMPER-RESISTANT | | | RECEPTACLES. | | | | | | STEVEN KENNEDY, CBO | | | ASSISTANT BUILDING OFFICIAL | | | (561) 805-6710 | | | [email protected] | | | |
|