| 2018-03-07 13:45:26 | 1ST REVIEW: FBC 2017 6TH ED. RESIDENTIAL |
| | 1ST REVIEW FBC 2017 EXISTING BUILDING |
| | |
| | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN |
| | UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE |
| | OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE |
| | AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT |
| | IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND |
| | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| | TECHNICAL CODES. |
| | FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. ALL |
| | INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING |
| | DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR THE DESIGN. |
| | |
| | PROVIDE THE FOLLOWING MINIMUM INFORMATION: |
| | |
| | FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3. |
| | SPECIFICALLY, PROVIDE A DOOR SUBMITTAL. |
| | FBC 107.3.5.1.1(8) - PROVIDE WIND DESIGN LOADS/DESIGN |
| | PRESSURES PURSUANT TO FBC-CHAPTER 16 |
| | FBC 107.3.5.3 - PROVIDE WIND DESIGN LOADS/DESIGN |
| | PRESSURES PURSUANT TO FBC-R301.2. |
| | FBC 107.3.5.3 ? INDICATE THE MEANS OF TERMITE |
| | PROTECTION PROPOSED PURSUANT TO FBC-R318. |
| | FBC 107 - PROVIDE DETAILS FOR THE CONSTRICTION OF |
| | EXTERIOR WALLS:EG SHOW IF BLOCK AND SHOW STEEL |
| | RE-INFORCING SIZE AND SPACING AND METHOD OF CONNECTION |
| | TO EXISTING STRUCTURE. SHOW EXISTING OR PROPOSED |
| | ADDITIONAL FOOTINGS FOR EXTERIOR WALL AREA. SHOW THE |
| | FINISH OF INTERIOR AND EXTERIOR WALLS. SHOW ANY |
| | PROPOSED ADDITION AND MEANS OF RAISING THE EXISTING |
| | FLOOR AREA. WILL CONCRETE BE ADDED. WILL THE FLOOR BE |
| | LEVELED? SHOW ANY PROPOSED LANDING FOR THE EXTERIOR OF |
| | PROPOSED NEW DOOR. NOTE A MINIMUM 3 FEET LONG LANDING |
| | IS REQUIRED ALONG THE WIDTH OF THE OPENING. |
| | FBC - R301.2.1.2 PROTECTION OF OPENINGS. SHOW METHOD OF |
| | IMPACT PROTECTION FOR GLAZING IF NOT IMPACT RESISTANT. |
| | FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE. |
| | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402 |
| | SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO |
| | DEMONSTRATE CODE COMPLIANCE BY THIS METHOD. |
| | |
| | |
| | STEVEN KENNEDY, CBO |
| | ASSISTANT BUILDING OFFICIAL |