Plan Review Notes
Plan Review Notes For Permit 18020359
Permit Number 18020359
Review Stop P
Sequence Number 5
Notes
Date Text
2018-12-11 16:56:12PLUMBING PROVISO: SHALL COMPLY PRIOR TO 1ST ROUGH
 INSPECTION.
  
 1. PROVIDE TEMPERED WATER AT THE LAVATORY.
 FBC PL 416.5 TEMPERED WATER SHALL BE DELIVERED FROM
 LAVATORIES AND GROUP WASH FIXTURES LOCATED IN PUBLIC
 TOILET FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3.
 FBC PL 607.1 HOT OR TEMPERED WATER WHERE REQUIRED. IN
 NONRESIDENTIAL OCCUPANCIES, HOT WATER SHALL BE SUPPLIED
 FOR CULINARY PURPOSES, CLEANSING, LAUNDRY OR BUILDING
 MAINTENANCE PURPOSES. IN NONRESIDENTIAL OCCUPANCIES,
 HOT WATER OR TEMPERED WATER SHALL BE SUPPLIED FOR
 BATHING AND WASHING PURPOSES.
 2. FBC ACC 604.7 TOILET PAPER DISPENSERS SHALL COMPLY
 WITH 309.4 AND SHALL BE 7 INCHES MINIMUM AND 9 INCHES
 MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO THE
 CENTERLINE OF THE DISPENSER.
 3. FBC ACC 609.4 GRAB BARS SHALL BE INSTALLED IN A
 HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE.
 4. A WATER FOUNTAIN AND SERVICE SINK ARE REQUIRED PER
 FBC PL TABLE 403.1
  
  